| 123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184185186187188189190191192193194195196197198199200201202203204205206207208209210211212213214215216217218219220221222223224225226227228229230231232233234235236237238239240241242243244245246247248249250251252253254255256257258259260261262263264265266267268269270271272273274275276 |
- 1
- 00:00:00,000 --> 00:00:03,040
- GW12型500千伏隔离刀闸
- 2
- 00:00:03,040 --> 00:00:05,600
- 是用在户外高压配电设备线路上
- 3
- 00:00:05,600 --> 00:00:06,815
- 配合断路器
- 4
- 00:00:06,815 --> 00:00:07,915
- 用于供线路
- 5
- 00:00:07,915 --> 00:00:08,890
- 在有电压
- 6
- 00:00:08,890 --> 00:00:10,950
- 无负载时开合电路之用
- 7
- 00:00:10,950 --> 00:00:12,533
- 它由三套独立的系统
- 8
- 00:00:12,533 --> 00:00:14,553
- 组成三相线路的开合
- 9
- 00:00:14,553 --> 00:00:16,198
- 可单体结构的开关
- 10
- 00:00:16,198 --> 00:00:17,828
- 也可三级联动控制
- 11
- 00:00:17,828 --> 00:00:18,713
- 控制灵活
- 12
- 00:00:18,720 --> 00:00:21,615
- 它的进出线装设在两端绝缘子上端
- 13
- 00:00:21,615 --> 00:00:24,440
- 分为用于电能转换为机械能的操作机构
- 14
- 00:00:24,440 --> 00:00:26,333
- 和用于分合闸的执行机构
- 15
- 00:00:26,333 --> 00:00:28,393
- 触头设有前端引弧装置
- 16
- 00:00:28,393 --> 00:00:29,903
- 防止破坏触头
- 17
- 00:00:29,903 --> 00:00:31,388
- 配备有过中弹簧
- 18
- 00:00:31,388 --> 00:00:32,898
- 可实现快速开合
- 19
- 00:00:32,906 --> 00:00:33,936
- 并能锁紧
- 20
- 00:00:33,936 --> 00:00:35,771
- 防止大电流发热现象
- 21
- 00:00:35,771 --> 00:00:38,693
- 触头和绝缘套筒之间均配有均压环
- 22
- 00:00:38,693 --> 00:00:41,318
- 可让活动触头间电压分布均匀
- 23
- 00:00:41,318 --> 00:00:43,088
- 减少了放电的可能性
- 24
- 00:00:43,088 --> 00:00:44,833
- 两端均装设接地开关
- 25
- 00:00:44,840 --> 00:00:46,065
- 可单独控制
- 26
- 00:00:46,065 --> 00:00:47,710
- 也可一起联动控制
- 27
- 00:00:47,710 --> 00:00:48,730
- 接地明显
- 28
- 00:00:48,730 --> 00:00:50,645
- 方便线路检修的同时
- 29
- 00:00:50,645 --> 00:00:51,780
- 还增加了安全性
- 30
- 00:00:52,267 --> 00:00:53,237
- 合闸时
- 31
- 00:00:53,237 --> 00:00:54,242
- 电机运转
- 32
- 00:00:54,242 --> 00:00:56,482
- 将电能转换为数轴的旋转
- 33
- 00:00:56,482 --> 00:00:58,202
- 带动旋转瓷瓶旋转
- 34
- 00:00:58,202 --> 00:00:59,907
- 迫使大臂做切线运动
- 35
- 00:00:59,907 --> 00:01:01,792
- 经齿盘拉伸平直二臂
- 36
- 00:01:01,792 --> 00:01:03,527
- 舒展向静触头运动
- 37
- 00:01:03,527 --> 00:01:05,813
- 此时过半弹簧一起储存能量
- 38
- 00:01:05,813 --> 00:01:08,068
- 首先到达的是尖端引弧头
- 39
- 00:01:08,068 --> 00:01:09,113
- 通过引弧
- 40
- 00:01:09,113 --> 00:01:11,440
- 保护动触头免受电弧伤害
- 41
- 00:01:11,466 --> 00:01:13,516
- 让其安全的接触静触头
- 42
- 00:01:13,516 --> 00:01:15,981
- 此时大臂触头压缩二臂触杆
- 43
- 00:01:15,981 --> 00:01:17,294
- 实现夹紧运动
- 44
- 00:01:17,294 --> 00:01:19,064
- 并为臂内弹簧储能
- 45
- 00:01:19,064 --> 00:01:19,979
- 分闸时
- 46
- 00:01:19,979 --> 00:01:21,484
- 只需让电机反转
- 47
- 00:01:21,484 --> 00:01:23,481
- 大臂触头释放二臂触杆
- 48
- 00:01:23,481 --> 00:01:24,871
- 在弹簧作用下
- 49
- 00:01:24,871 --> 00:01:25,911
- 触头松开
- 50
- 00:01:25,911 --> 00:01:28,471
- 在机械能和过半弹簧的能量下
- 51
- 00:01:28,471 --> 00:01:29,406
- 迅速受缩
- 52
- 00:01:29,414 --> 00:01:30,641
- 直到大臂和
- 53
- 00:01:30,641 --> 00:01:32,091
- 二臂竖直完成
- 54
- 00:01:32,091 --> 00:01:34,706
- 当线路需要检修或者冷储备时
- 55
- 00:01:34,706 --> 00:01:36,627
- 我们可以将接地刀闸合闸
- 56
- 00:01:36,627 --> 00:01:39,057
- 接地系统的操作机构电机运转
- 57
- 00:01:39,057 --> 00:01:40,397
- 带动数轴运转
- 58
- 00:01:40,397 --> 00:01:42,977
- 经连杆带动接地大臂做切线运动
- 59
- 00:01:42,987 --> 00:01:44,937
- 经齿轮带动二臂伸展
- 60
- 00:01:44,937 --> 00:01:47,182
- 期间大臂内部弹簧储能
- 61
- 00:01:47,182 --> 00:01:49,294
- 直到触头插入静触筒位置
- 62
- 00:01:49,294 --> 00:01:51,241
- 可靠明显的接地系统
- 63
- 00:01:51,241 --> 00:01:54,541
- 提升了我们倒闸操作的严谨性和安全性
- 64
- 00:01:54,541 --> 00:01:56,947
- 利于我们对高电压的控制和维护
- 65
- 00:01:56,947 --> 00:01:58,147
- 伸缩式结构
- 66
- 00:01:58,147 --> 00:02:00,782
- 让使我们的空间利用率大大提高
- 67
- 00:02:00,782 --> 00:02:04,001
- 其具有开断、关合小电感、电容电流的优势
- 68
- 00:02:04,001 --> 00:02:07,156
- 广范应用于500千伏线路及以上线路
- 69
- 00:02:07,156 --> 00:02:10,734
- 以上就是500千伏隔离刀闸的构造和工作原理
|