10kV真空断路器二次原理储能回路解析.srt 1.3 KB

12345678910111213141516171819202122232425262728293031323334353637383940414243444546474849505152535455565758596061626364656667686970717273747576777879808182838485868788
  1. 1
  2. 00:00:00,000 --> 00:00:03,360
  3. 通过旋钮KK打到手动或者自动储能
  4. 2
  5. 00:00:03,360 --> 00:00:04,790
  6. 当达到手动时
  7. 3
  8. 00:00:04,790 --> 00:00:06,760
  9. 201和203接通
  10. 4
  11. 00:00:06,760 --> 00:00:08,100
  12. 按动储能按钮
  13. 5
  14. 00:00:08,100 --> 00:00:09,110
  15. 205的电
  16. 6
  17. 00:00:09,110 --> 00:00:10,550
  18. 通过航空插头
  19. 7
  20. 00:00:10,550 --> 00:00:13,510
  21. 到达储能电机合闸到位的常闭点
  22. 8
  23. 00:00:13,520 --> 00:00:15,540
  24. 该常闭点有两个功能
  25. 9
  26. 00:00:15,540 --> 00:00:18,660
  27. 一是防止储能到位是再次接通储能
  28. 10
  29. 00:00:18,660 --> 00:00:21,706
  30. 二是当储能电机储能到位时它分开
  31. 11
  32. 00:00:21,706 --> 00:00:23,666
  33. 从而让储能电机停止
  34. 12
  35. 00:00:23,666 --> 00:00:25,986
  36. 储能电机运转储能弹簧
  37. 13
  38. 00:00:25,986 --> 00:00:26,986
  39. 当到位时
  40. 14
  41. 00:00:26,986 --> 00:00:28,666
  42. 常闭点变常开点
  43. 15
  44. 00:00:28,666 --> 00:00:30,046
  45. 储能电机停止
  46. 16
  47. 00:00:30,046 --> 00:00:31,916
  48. 当旋钮打到自动时
  49. 17
  50. 00:00:31,916 --> 00:00:33,566
  51. 电到达 205
  52. 18
  53. 00:00:33,566 --> 00:00:35,876
  54. 如果未储能或者储能未到位
  55. 19
  56. 00:00:35,880 --> 00:00:38,170
  57. 都会让储能电机自己运转
  58. 20
  59. 00:00:38,170 --> 00:00:40,380
  60. 当储能完毕后自己停止
  61. 21
  62. 00:00:40,380 --> 00:00:42,920
  63. 如果再次合闸释放了储能能量
  64. 22
  65. 00:00:42,920 --> 00:00:46,680
  66. 由于205一直带电 储能电机会自己运转