| 12345678910111213141516171819202122232425262728293031323334353637383940414243444546474849505152535455565758596061626364656667686970717273747576777879808182838485868788 |
- 1
- 00:00:00,000 --> 00:00:03,360
- 通过旋钮KK打到手动或者自动储能
- 2
- 00:00:03,360 --> 00:00:04,790
- 当达到手动时
- 3
- 00:00:04,790 --> 00:00:06,760
- 201和203接通
- 4
- 00:00:06,760 --> 00:00:08,100
- 按动储能按钮
- 5
- 00:00:08,100 --> 00:00:09,110
- 205的电
- 6
- 00:00:09,110 --> 00:00:10,550
- 通过航空插头
- 7
- 00:00:10,550 --> 00:00:13,510
- 到达储能电机合闸到位的常闭点
- 8
- 00:00:13,520 --> 00:00:15,540
- 该常闭点有两个功能
- 9
- 00:00:15,540 --> 00:00:18,660
- 一是防止储能到位是再次接通储能
- 10
- 00:00:18,660 --> 00:00:21,706
- 二是当储能电机储能到位时它分开
- 11
- 00:00:21,706 --> 00:00:23,666
- 从而让储能电机停止
- 12
- 00:00:23,666 --> 00:00:25,986
- 储能电机运转储能弹簧
- 13
- 00:00:25,986 --> 00:00:26,986
- 当到位时
- 14
- 00:00:26,986 --> 00:00:28,666
- 常闭点变常开点
- 15
- 00:00:28,666 --> 00:00:30,046
- 储能电机停止
- 16
- 00:00:30,046 --> 00:00:31,916
- 当旋钮打到自动时
- 17
- 00:00:31,916 --> 00:00:33,566
- 电到达 205
- 18
- 00:00:33,566 --> 00:00:35,876
- 如果未储能或者储能未到位
- 19
- 00:00:35,880 --> 00:00:38,170
- 都会让储能电机自己运转
- 20
- 00:00:38,170 --> 00:00:40,380
- 当储能完毕后自己停止
- 21
- 00:00:40,380 --> 00:00:42,920
- 如果再次合闸释放了储能能量
- 22
- 00:00:42,920 --> 00:00:46,680
- 由于205一直带电 储能电机会自己运转
|