220kV变压器-机械特性-old.srt 5.7 KB

123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184185186187188189190191192193194195196197198199200201202203204205206207208209210211212213214215216217218219220221222223224225226227228229230231232233234235236237238239240241242243244245246247248249250251252253254255256257258259260261262263264265266267268269270271272273274275276277278279280281282283284285286287288289290291292293294295296297298299300301302303304305306307308309310311312313314315316317318319320321322323324325326327328329330331332333334335336
  1. 1
  2. 00:00:00,000 --> 00:00:05,290
  3. 220千伏有载调压开关是一种可在空载和带负荷条件下
  4. 2
  5. 00:00:05,290 --> 00:00:08,826
  6. 无需停电即可调整变压器输出电压的装置
  7. 3
  8. 00:00:08,826 --> 00:00:12,496
  9. 通过分接头档位转换调节高压绕组匝数
  10. 4
  11. 00:00:12,496 --> 00:00:14,166
  12. 从而改变负荷侧电压
  13. 5
  14. 00:00:14,720 --> 00:00:17,250
  15. 由于越靠近中性点电压越低
  16. 6
  17. 00:00:17,250 --> 00:00:20,300
  18. 该调压开关通过改变中性点匝数
  19. 7
  20. 00:00:20,300 --> 00:00:22,013
  21. 以及通过范围开关
  22. 8
  23. 00:00:22,013 --> 00:00:23,613
  24. 选择线圈方向
  25. 9
  26. 00:00:23,613 --> 00:00:25,153
  27. 加位或者减位
  28. 10
  29. 00:00:25,153 --> 00:00:26,813
  30. 来转换电流方向
  31. 11
  32. 00:00:26,813 --> 00:00:29,013
  33. 选择增大或者抵消磁场
  34. 12
  35. 00:00:29,013 --> 00:00:31,346
  36. 使调节倍数增加一倍
  37. 13
  38. 00:00:31,347 --> 00:00:34,027
  39. 它分为操作系统和执行系统
  40. 14
  41. 00:00:34,027 --> 00:00:37,587
  42. 操作系统通过电机或手动转动提供动力
  43. 15
  44. 00:00:37,587 --> 00:00:40,307
  45. 执行机构用于切换绕组匝数
  46. 16
  47. 00:00:40,307 --> 00:00:44,040
  48. 其中执行机构由选择开关和切换开关组成
  49. 17
  50. 00:00:44,040 --> 00:00:47,790
  51. 选择开关连接各个调节的不同匝数的绕组
  52. 18
  53. 00:00:47,790 --> 00:00:49,500
  54. 分别为1-8号抽头
  55. 19
  56. 00:00:50,067 --> 00:00:51,577
  57. 在三相系统中
  58. 20
  59. 00:00:51,577 --> 00:00:53,397
  60. 每相又分为两层
  61. 21
  62. 00:00:53,397 --> 00:00:55,987
  63. 上层为奇数1357抽头
  64. 22
  65. 00:00:55,987 --> 00:01:00,547
  66. 下层为号偶数2468号抽头和一个范围开关共用抽头
  67. 23
  68. 00:01:00,547 --> 00:01:03,847
  69. 用于选择需调节的绕组和绕组的方向
  70. 24
  71. 00:01:03,847 --> 00:01:06,387
  72. 也用于预选需要转换的匝数
  73. 25
  74. 00:01:06,387 --> 00:01:08,937
  75. 切换开关主要是将选择的匝数
  76. 26
  77. 00:01:08,947 --> 00:01:11,747
  78. 每个绕组四个共12个触头
  79. 27
  80. 00:01:11,747 --> 00:01:13,247
  81. 通过步进方式
  82. 28
  83. 00:01:13,247 --> 00:01:15,197
  84. 让一组或两组接通
  85. 29
  86. 00:01:15,197 --> 00:01:16,937
  87. 中间经过渡电阻
  88. 30
  89. 00:01:16,937 --> 00:01:18,907
  90. 顺利切换到预选匝数
  91. 31
  92. 00:01:18,907 --> 00:01:22,097
  93. 后经中性点线排回到变压器中性点
  94. 32
  95. 00:01:22,097 --> 00:01:24,807
  96. 接下来让我们演示一下它的操作方法
  97. 33
  98. 00:01:25,361 --> 00:01:27,191
  99. 假设我们现在为一档
  100. 34
  101. 00:01:27,191 --> 00:01:28,901
  102. 想降低负载电压
  103. 35
  104. 00:01:28,901 --> 00:01:30,171
  105. 调节到二档
  106. 36
  107. 00:01:30,171 --> 00:01:32,041
  108. 由于遵循抵挡绕组少
  109. 37
  110. 00:01:32,041 --> 00:01:33,351
  111. 高档绕组多
  112. 38
  113. 00:01:33,351 --> 00:01:36,251
  114. 那么此时范围开关是在加档位置
  115. 39
  116. 00:01:36,251 --> 00:01:39,381
  117. 而选择开关绕组在 下层1号抽头位置
  118. 40
  119. 00:01:39,948 --> 00:01:42,928
  120. 我们手动摇动转动或者电机转动
  121. 41
  122. 00:01:42,928 --> 00:01:44,228
  123. 经竖轴运动
  124. 42
  125. 00:01:44,228 --> 00:01:45,358
  126. 横轴运动
  127. 43
  128. 00:01:45,358 --> 00:01:48,494
  129. 带动调压开关的选择开关的主轴运动
  130. 44
  131. 00:01:48,494 --> 00:01:49,934
  132. 经旋转齿盘
  133. 45
  134. 00:01:49,934 --> 00:01:52,884
  135. 拨动下端选择开关齿盘主轴运动
  136. 46
  137. 00:01:52,884 --> 00:01:55,494
  138. 让预选连接上层2号抽头绕组
  139. 47
  140. 00:01:56,055 --> 00:01:59,455
  141. 同时上端主轴带动切换开关快慢机
  142. 48
  143. 00:01:59,455 --> 00:02:02,925
  144. 使得触头中间的尾推弹簧机构有节奏的运动
  145. 49
  146. 00:02:03,482 --> 00:02:06,822
  147. 现在我们面临的情况是1号绕组连接第一个
  148. 50
  149. 00:02:06,822 --> 00:02:08,572
  150. 触头到达中性点
  151. 51
  152. 00:02:08,572 --> 00:02:11,562
  153. 预选2号绕组连接在第四个触头上
  154. 52
  155. 00:02:11,562 --> 00:02:15,672
  156. 我们的目的是从第一个触头改变成第四个触头
  157. 53
  158. 00:02:15,672 --> 00:02:17,842
  159. 我们首先连接第二个触头
  160. 54
  161. 00:02:17,842 --> 00:02:19,842
  162. 然后断开第一个触头
  163. 55
  164. 00:02:19,842 --> 00:02:24,482
  165. 此时电经1号绕组和第二个触头经渡电阻到达中性点
  166. 56
  167. 00:02:24,482 --> 00:02:26,322
  168. 接通第三个触头
  169. 57
  170. 00:02:26,322 --> 00:02:28,972
  171. 此时电经1号绕组和2号绕组
  172. 58
  173. 00:02:28,972 --> 00:02:32,032
  174. 并联经过渡电阻缓冲到达中性点
  175. 59
  176. 00:02:32,032 --> 00:02:33,442
  177. 断开第二个触头
  178. 60
  179. 00:02:33,442 --> 00:02:38,622
  180. 此时电经二档绕组和第三个触头及过渡电阻到达中性点
  181. 61
  182. 00:02:38,622 --> 00:02:40,202
  183. 连接第四个触头
  184. 62
  185. 00:02:40,202 --> 00:02:41,852
  186. 断开第三个触头
  187. 63
  188. 00:02:41,852 --> 00:02:46,062
  189. 此时电经2号绕组经第四个触头到达中性点
  190. 64
  191. 00:02:46,062 --> 00:02:48,332
  192. 这就变压器经有载调压开关
  193. 65
  194. 00:02:48,332 --> 00:02:50,632
  195. 顺利从一档调节到二档的位置
  196. 66
  197. 00:02:51,189 --> 00:02:52,559
  198. 需要注意的是
  199. 67
  200. 00:02:52,559 --> 00:02:55,509
  201. 有载调压开关是不能跳档调节的
  202. 68
  203. 00:02:55,509 --> 00:02:57,269
  204. 只逐步一档一档调节
  205. 69
  206. 00:02:57,269 --> 00:03:00,495
  207. 当八档到九档时情况会比较特殊
  208. 70
  209. 00:03:00,496 --> 00:03:03,906
  210. 9档分为9A、9B和9C共三档
  211. 71
  212. 00:03:03,906 --> 00:03:06,426
  213. 9B为极性转换的标准档位
  214. 72
  215. 00:03:06,426 --> 00:03:07,602
  216. 可长期运转
  217. 73
  218. 00:03:07,602 --> 00:03:12,696
  219. 9A、9C为过渡档位 只可临时运行不可长期运行
  220. 74
  221. 00:03:12,696 --> 00:03:14,886
  222. 这就顺利的从加档位置
  223. 75
  224. 00:03:14,886 --> 00:03:16,716
  225. 切换到了减档位置
  226. 76
  227. 00:03:16,716 --> 00:03:19,696
  228. 从十档开始直至加到十七档的过程
  229. 77
  230. 00:03:19,696 --> 00:03:22,956
  231. 是从1号绕组到8号绕组中的切换
  232. 78
  233. 00:03:22,956 --> 00:03:25,006
  234. 完成1到17档的切换
  235. 79
  236. 00:03:25,006 --> 00:03:26,886
  237. 完成负载的降压过程
  238. 80
  239. 00:03:26,896 --> 00:03:28,926
  240. 而减档责恰恰相反
  241. 81
  242. 00:03:28,926 --> 00:03:31,066
  243. 通过手动或电机反转
  244. 82
  245. 00:03:31,066 --> 00:03:32,356
  246. 来升高负载的电压
  247. 83
  248. 00:03:32,910 --> 00:03:36,430
  249. 下面为17档切换至1档的运动状态
  250. 84
  251. 00:03:36,430 --> 00:03:41,176