| 123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184185186187188189190191192193194195196197198199200201202203204205206207208209210211212213214215216217218219220221222223224225226227228229230231232233234235236237238239240241242243244245246247248249250251252253254255256257258259260261262263264265266267268269270271272273274275276277278279280281282283284285286287288289290291292293294295296297298299300301302303304305306307308309310311312313314315316317318319320321322323324325326327328329330331332333334335336 |
- 1
- 00:00:00,000 --> 00:00:05,290
- 220千伏有载调压开关是一种可在空载和带负荷条件下
- 2
- 00:00:05,290 --> 00:00:08,826
- 无需停电即可调整变压器输出电压的装置
- 3
- 00:00:08,826 --> 00:00:12,496
- 通过分接头档位转换调节高压绕组匝数
- 4
- 00:00:12,496 --> 00:00:14,166
- 从而改变负荷侧电压
- 5
- 00:00:14,720 --> 00:00:17,250
- 由于越靠近中性点电压越低
- 6
- 00:00:17,250 --> 00:00:20,300
- 该调压开关通过改变中性点匝数
- 7
- 00:00:20,300 --> 00:00:22,013
- 以及通过范围开关
- 8
- 00:00:22,013 --> 00:00:23,613
- 选择线圈方向
- 9
- 00:00:23,613 --> 00:00:25,153
- 加位或者减位
- 10
- 00:00:25,153 --> 00:00:26,813
- 来转换电流方向
- 11
- 00:00:26,813 --> 00:00:29,013
- 选择增大或者抵消磁场
- 12
- 00:00:29,013 --> 00:00:31,346
- 使调节倍数增加一倍
- 13
- 00:00:31,347 --> 00:00:34,027
- 它分为操作系统和执行系统
- 14
- 00:00:34,027 --> 00:00:37,587
- 操作系统通过电机或手动转动提供动力
- 15
- 00:00:37,587 --> 00:00:40,307
- 执行机构用于切换绕组匝数
- 16
- 00:00:40,307 --> 00:00:44,040
- 其中执行机构由选择开关和切换开关组成
- 17
- 00:00:44,040 --> 00:00:47,790
- 选择开关连接各个调节的不同匝数的绕组
- 18
- 00:00:47,790 --> 00:00:49,500
- 分别为1-8号抽头
- 19
- 00:00:50,067 --> 00:00:51,577
- 在三相系统中
- 20
- 00:00:51,577 --> 00:00:53,397
- 每相又分为两层
- 21
- 00:00:53,397 --> 00:00:55,987
- 上层为奇数1357抽头
- 22
- 00:00:55,987 --> 00:01:00,547
- 下层为号偶数2468号抽头和一个范围开关共用抽头
- 23
- 00:01:00,547 --> 00:01:03,847
- 用于选择需调节的绕组和绕组的方向
- 24
- 00:01:03,847 --> 00:01:06,387
- 也用于预选需要转换的匝数
- 25
- 00:01:06,387 --> 00:01:08,937
- 切换开关主要是将选择的匝数
- 26
- 00:01:08,947 --> 00:01:11,747
- 每个绕组四个共12个触头
- 27
- 00:01:11,747 --> 00:01:13,247
- 通过步进方式
- 28
- 00:01:13,247 --> 00:01:15,197
- 让一组或两组接通
- 29
- 00:01:15,197 --> 00:01:16,937
- 中间经过渡电阻
- 30
- 00:01:16,937 --> 00:01:18,907
- 顺利切换到预选匝数
- 31
- 00:01:18,907 --> 00:01:22,097
- 后经中性点线排回到变压器中性点
- 32
- 00:01:22,097 --> 00:01:24,807
- 接下来让我们演示一下它的操作方法
- 33
- 00:01:25,361 --> 00:01:27,191
- 假设我们现在为一档
- 34
- 00:01:27,191 --> 00:01:28,901
- 想降低负载电压
- 35
- 00:01:28,901 --> 00:01:30,171
- 调节到二档
- 36
- 00:01:30,171 --> 00:01:32,041
- 由于遵循抵挡绕组少
- 37
- 00:01:32,041 --> 00:01:33,351
- 高档绕组多
- 38
- 00:01:33,351 --> 00:01:36,251
- 那么此时范围开关是在加档位置
- 39
- 00:01:36,251 --> 00:01:39,381
- 而选择开关绕组在 下层1号抽头位置
- 40
- 00:01:39,948 --> 00:01:42,928
- 我们手动摇动转动或者电机转动
- 41
- 00:01:42,928 --> 00:01:44,228
- 经竖轴运动
- 42
- 00:01:44,228 --> 00:01:45,358
- 横轴运动
- 43
- 00:01:45,358 --> 00:01:48,494
- 带动调压开关的选择开关的主轴运动
- 44
- 00:01:48,494 --> 00:01:49,934
- 经旋转齿盘
- 45
- 00:01:49,934 --> 00:01:52,884
- 拨动下端选择开关齿盘主轴运动
- 46
- 00:01:52,884 --> 00:01:55,494
- 让预选连接上层2号抽头绕组
- 47
- 00:01:56,055 --> 00:01:59,455
- 同时上端主轴带动切换开关快慢机
- 48
- 00:01:59,455 --> 00:02:02,925
- 使得触头中间的尾推弹簧机构有节奏的运动
- 49
- 00:02:03,482 --> 00:02:06,822
- 现在我们面临的情况是1号绕组连接第一个
- 50
- 00:02:06,822 --> 00:02:08,572
- 触头到达中性点
- 51
- 00:02:08,572 --> 00:02:11,562
- 预选2号绕组连接在第四个触头上
- 52
- 00:02:11,562 --> 00:02:15,672
- 我们的目的是从第一个触头改变成第四个触头
- 53
- 00:02:15,672 --> 00:02:17,842
- 我们首先连接第二个触头
- 54
- 00:02:17,842 --> 00:02:19,842
- 然后断开第一个触头
- 55
- 00:02:19,842 --> 00:02:24,482
- 此时电经1号绕组和第二个触头经渡电阻到达中性点
- 56
- 00:02:24,482 --> 00:02:26,322
- 接通第三个触头
- 57
- 00:02:26,322 --> 00:02:28,972
- 此时电经1号绕组和2号绕组
- 58
- 00:02:28,972 --> 00:02:32,032
- 并联经过渡电阻缓冲到达中性点
- 59
- 00:02:32,032 --> 00:02:33,442
- 断开第二个触头
- 60
- 00:02:33,442 --> 00:02:38,622
- 此时电经二档绕组和第三个触头及过渡电阻到达中性点
- 61
- 00:02:38,622 --> 00:02:40,202
- 连接第四个触头
- 62
- 00:02:40,202 --> 00:02:41,852
- 断开第三个触头
- 63
- 00:02:41,852 --> 00:02:46,062
- 此时电经2号绕组经第四个触头到达中性点
- 64
- 00:02:46,062 --> 00:02:48,332
- 这就变压器经有载调压开关
- 65
- 00:02:48,332 --> 00:02:50,632
- 顺利从一档调节到二档的位置
- 66
- 00:02:51,189 --> 00:02:52,559
- 需要注意的是
- 67
- 00:02:52,559 --> 00:02:55,509
- 有载调压开关是不能跳档调节的
- 68
- 00:02:55,509 --> 00:02:57,269
- 只逐步一档一档调节
- 69
- 00:02:57,269 --> 00:03:00,495
- 当八档到九档时情况会比较特殊
- 70
- 00:03:00,496 --> 00:03:03,906
- 9档分为9A、9B和9C共三档
- 71
- 00:03:03,906 --> 00:03:06,426
- 9B为极性转换的标准档位
- 72
- 00:03:06,426 --> 00:03:07,602
- 可长期运转
- 73
- 00:03:07,602 --> 00:03:12,696
- 9A、9C为过渡档位 只可临时运行不可长期运行
- 74
- 00:03:12,696 --> 00:03:14,886
- 这就顺利的从加档位置
- 75
- 00:03:14,886 --> 00:03:16,716
- 切换到了减档位置
- 76
- 00:03:16,716 --> 00:03:19,696
- 从十档开始直至加到十七档的过程
- 77
- 00:03:19,696 --> 00:03:22,956
- 是从1号绕组到8号绕组中的切换
- 78
- 00:03:22,956 --> 00:03:25,006
- 完成1到17档的切换
- 79
- 00:03:25,006 --> 00:03:26,886
- 完成负载的降压过程
- 80
- 00:03:26,896 --> 00:03:28,926
- 而减档责恰恰相反
- 81
- 00:03:28,926 --> 00:03:31,066
- 通过手动或电机反转
- 82
- 00:03:31,066 --> 00:03:32,356
- 来升高负载的电压
- 83
- 00:03:32,910 --> 00:03:36,430
- 下面为17档切换至1档的运动状态
- 84
- 00:03:36,430 --> 00:03:41,176
- 以上就是220千伏有载调压开关的构造和工作原理
|