VS1真空断路器-燃弧息弧.srt 1.3 KB

1234567891011121314151617181920212223242526272829303132333435363738394041424344454647484950515253545556575859606162636465666768697071727374757677787980
  1. 1
  2. 00:00:00,000 --> 00:00:05,590
  3. VS1真空断路器因其灭弧介质和灭弧后触头间隙的绝缘介质
  4. 2
  5. 00:00:05,590 --> 00:00:07,160
  6. 都是真空而得名
  7. 3
  8. 00:00:07,160 --> 00:00:10,480
  9. 适用于频繁操作、灭弧不用检修
  10. 4
  11. 00:00:10,480 --> 00:00:12,455
  12. 当断路器断开瞬间
  13. 5
  14. 00:00:12,455 --> 00:00:14,065
  15. 静动触头分离
  16. 6
  17. 00:00:14,065 --> 00:00:15,330
  18. 形成电弧
  19. 7
  20. 00:00:15,330 --> 00:00:18,066
  21. 高真空环境有效抑制电子游离
  22. 8
  23. 00:00:18,066 --> 00:00:21,281
  24. 触头锤头式加接触面波浪纹设计
  25. 9
  26. 00:00:21,281 --> 00:00:23,706
  27. 让电弧成多个爆炸式发散
  28. 10
  29. 00:00:23,706 --> 00:00:25,201
  30. 在电场的干扰下
  31. 11
  32. 00:00:25,213 --> 00:00:29,163
  33. 让金属快速横向向外层金属屏蔽层运动
  34. 12
  35. 00:00:29,163 --> 00:00:31,383
  36. 在屏蔽层快速凝结
  37. 13
  38. 00:00:31,383 --> 00:00:34,958
  39. 高真空环境下气体分子平均自由程变大
  40. 14
  41. 00:00:34,960 --> 00:00:36,835
  42. 碰撞游离概率低
  43. 15
  44. 00:00:36,835 --> 00:00:40,030
  45. 绝缘强度比常规气体高数十倍
  46. 16
  47. 00:00:40,030 --> 00:00:42,200
  48. 使介电强度迅速回复
  49. 17
  50. 00:00:42,200 --> 00:00:44,360
  51. 以及随着距离的增大
  52. 18
  53. 00:00:44,360 --> 00:00:46,405
  54. 从而让电流过零时
  55. 19
  56. 00:00:46,405 --> 00:00:48,035
  57. 迅速切断电弧
  58. 20
  59. 00:00:48,035 --> 00:00:49,773
  60. 且不会再次击穿