220kV断路器-二次回路原理-old.srt 4.0 KB

123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184185186187188189190191192193194195196197198199200201202203204205206207208209210211212213214215216217218219220221222223224225226227228229230231232233234235236237238239240241242243244
  1. 1
  2. 00:00:00,000 --> 00:00:03,660
  3. 1:该二次线路具备手动本地分合闸功能
  4. 2
  5. 00:00:03,660 --> 00:00:04,910
  6. 用于本地操作
  7. 3
  8. 00:00:04,910 --> 00:00:06,080
  9. 远程分合闸
  10. 4
  11. 00:00:06,080 --> 00:00:10,960
  12. 用于远程自动化或者国网平台或者远控箱分合闸功能
  13. 5
  14. 00:00:10,960 --> 00:00:14,250
  15. 当分合闸旋钮kk打到本地控制时
  16. 6
  17. 00:00:14,250 --> 00:00:15,910
  18. 可旋至手动合闸
  19. 7
  20. 00:00:15,910 --> 00:00:17,706
  21. 让KK1   2接通
  22. 8
  23. 00:00:17,706 --> 00:00:21,120
  24. 使合闸线圈HQ吸合 用于合闸
  25. 9
  26. 00:00:21,120 --> 00:00:27,480
  27. 当旋钮钮到分闸时 11   12端子接通 使分闸线圈TQ跳闸
  28. 10
  29. 00:00:27,480 --> 00:00:32,440
  30. 当选至远程时5      6端子接通 7      8端子接通
  31. 11
  32. 00:00:32,440 --> 00:00:35,780
  33. 可用远程合闸入口和远程分闸入口
  34. 12
  35. 00:00:35,780 --> 00:00:37,170
  36. 接到国网平台
  37. 13
  38. 00:00:37,170 --> 00:00:38,140
  39. 远控箱去
  40. 14
  41. 00:00:38,140 --> 00:00:40,093
  42. 去分合闸断路器
  43. 15
  44. 00:00:40,094 -->00:00:40,095
  45. 16
  46. 00:00:40,095 --> 00:00:43,664
  47. 2:该线路可通过接入微机综合保护器
  48. 17
  49. 00:00:43,664 --> 00:00:46,724
  50. 让其具备两套独立的二次重合闸功能
  51. 18
  52. 00:00:46,724 --> 00:00:49,534
  53. 和两套独立的远程跳闸功能
  54. 19
  55. 00:00:49,534 --> 00:00:54,944
  56. 来自两套独立的微机保护器的重合闸常开点HJ1和HJ2
  57. 20
  58. 00:00:54,944 --> 00:00:56,494
  59. 可使意外跳闸时
  60. 21
  61. 00:00:56,494 --> 00:00:59,507
  62. 根据微保设置 来一次重合闸
  63. 22
  64. 00:00:59,508 --> 00:01:01,368
  65. 当不想利用该功能时
  66. 23
  67. 00:01:01,368 --> 00:01:02,598
  68. 或者检修时
  69. 24
  70. 00:01:02,598 --> 00:01:04,298
  71. 可挑其保护连片
  72. 25
  73. 00:01:04,298 --> 00:01:06,528
  74. 远程跳闸TJ1和TJ2
  75. 26
  76. 00:01:06,528 --> 00:01:10,321
  77. 保护跳闸入口可接入两套独立的微机保护
  78. 27
  79. 00:01:10,322 --> 00:01:12,282
  80. 或者其他保护继电器
  81. 28
  82. 00:01:12,282 --> 00:01:15,292
  83. 有的也会接入两套独立的跳闸线圈
  84. 29
  85. 00:01:15,292 --> 00:01:17,175
  86. 用于需要跳闸时的跳闸
  87. 30
  88. 00:01:17,175 --> 00:01:20,842
  89. 其中微机保护中的设置保护参数需一致
  90. 31
  91. 00:01:20,842 --> 00:01:20,843
  92. 32
  93. 00:01:20,843 --> 00:01:23,482
  94. 3:该线路具备防跳跃功能
  95. 33
  96. 00:01:23,482 --> 00:01:26,668
  97. TBJV继电器在断路器分闸时吸合
  98. 34
  99. 00:01:26,668 --> 00:01:29,598
  100. 通过它的辅助触点串入合闸回路
  101. 35
  102. 00:01:29,598 --> 00:01:33,642
  103. 防止在跳闸过程中又有合闸命令而损坏机构
  104. 36
  105. 00:01:33,642 --> 00:01:33,643
  106. 37
  107. 00:01:33,643 --> 00:01:37,752
  108. 4:KKJ是合后继电器也称磁保持继电器
  109. 38
  110. 00:01:37,752 --> 00:01:38,612
  111. 通过D1、
  112. 39
  113. 00:01:38,612 --> 00:01:42,932
  114. D2两个二极管的单相导通性能来保证只有手动合闸
  115. 40
  116. 00:01:42,932 --> 00:01:44,162
  117. 才能让其动作
  118. 41
  119. 00:01:44,162 --> 00:01:46,072
  120. 动作后不自动返回
  121. 42
  122. 00:01:46,072 --> 00:01:49,632
  123. 手动跳闸或者自动合闸后才能让其复归
  124. 43
  125. 00:01:49,642 --> 00:01:52,055
  126. 其接点可以用于重合闸
  127. 44
  128. 00:01:52,056 --> 00:01:52,057
  129. 45
  130. 00:01:52,057 --> 00:01:56,366
  131. 5:HYI与TYJ是合闸和跳闸压力继电器
  132. 46
  133. 00:01:56,366 --> 00:01:58,696
  134. 接入断路器机构的气压接点
  135. 47
  136. 00:01:58,696 --> 00:02:02,116
  137. 在以六氟化硫为灭弧绝缘介质的开关中
  138. 48
  139. 00:02:02,116 --> 00:02:04,429
  140. 如果六氟化硫气体有泄露
  141. 49
  142. 00:02:04,429 --> 00:02:09,189
  143. 则当气体压力降至危及灭弧时该接点T1和T2导通
  144. 50
  145. 00:02:09,189 --> 00:02:10,849
  146. 将操作回路断开
  147. 51
  148. 00:02:10,856 --> 00:02:12,176
  149. 禁止操作
  150. 52
  151. 00:02:12,176 --> 00:02:12,177
  152. 53
  153. 00:02:12,177 --> 00:02:14,316
  154. 6:位置继电器HWJ
  155. 54
  156. 00:02:14,316 --> 00:02:16,706
  157. TWT的作用有两个
  158. 55
  159. 00:02:16,706 --> 00:02:18,789
  160. 一是显示当前开关位置
  161. 56
  162. 00:02:18,789 --> 00:02:21,736
  163. 二是监视跳、合线圈是否完好
  164. 57
  165. 00:02:21,736 --> 00:02:21,737
  166. 58
  167. 00:02:21,737 --> 00:02:24,526
  168. 7:控制电源采双电源系统
  169. 59
  170. 00:02:24,526 --> 00:02:26,166
  171. 利用JJ继电器
  172. 60
  173. 00:02:26,166 --> 00:02:28,562
  174. 当一号直流屏电源KM1
  175. 61