| 123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184185186187188189190191192193194195196197198199200201202203204205206207208209210211212213214215216217218219220221222223224225226227228229230231232233234235236237238239240241242243244 |
- 1
- 00:00:00,000 --> 00:00:03,660
- 1:该二次线路具备手动本地分合闸功能
- 2
- 00:00:03,660 --> 00:00:04,910
- 用于本地操作
- 3
- 00:00:04,910 --> 00:00:06,080
- 远程分合闸
- 4
- 00:00:06,080 --> 00:00:10,960
- 用于远程自动化或者国网平台或者远控箱分合闸功能
- 5
- 00:00:10,960 --> 00:00:14,250
- 当分合闸旋钮kk打到本地控制时
- 6
- 00:00:14,250 --> 00:00:15,910
- 可旋至手动合闸
- 7
- 00:00:15,910 --> 00:00:17,706
- 让KK1 2接通
- 8
- 00:00:17,706 --> 00:00:21,120
- 使合闸线圈HQ吸合 用于合闸
- 9
- 00:00:21,120 --> 00:00:27,480
- 当旋钮钮到分闸时 11 12端子接通 使分闸线圈TQ跳闸
- 10
- 00:00:27,480 --> 00:00:32,440
- 当选至远程时5 6端子接通 7 8端子接通
- 11
- 00:00:32,440 --> 00:00:35,780
- 可用远程合闸入口和远程分闸入口
- 12
- 00:00:35,780 --> 00:00:37,170
- 接到国网平台
- 13
- 00:00:37,170 --> 00:00:38,140
- 远控箱去
- 14
- 00:00:38,140 --> 00:00:40,093
- 去分合闸断路器
- 15
- 00:00:40,094 -->00:00:40,095
-
- 16
- 00:00:40,095 --> 00:00:43,664
- 2:该线路可通过接入微机综合保护器
- 17
- 00:00:43,664 --> 00:00:46,724
- 让其具备两套独立的二次重合闸功能
- 18
- 00:00:46,724 --> 00:00:49,534
- 和两套独立的远程跳闸功能
- 19
- 00:00:49,534 --> 00:00:54,944
- 来自两套独立的微机保护器的重合闸常开点HJ1和HJ2
- 20
- 00:00:54,944 --> 00:00:56,494
- 可使意外跳闸时
- 21
- 00:00:56,494 --> 00:00:59,507
- 根据微保设置 来一次重合闸
- 22
- 00:00:59,508 --> 00:01:01,368
- 当不想利用该功能时
- 23
- 00:01:01,368 --> 00:01:02,598
- 或者检修时
- 24
- 00:01:02,598 --> 00:01:04,298
- 可挑其保护连片
- 25
- 00:01:04,298 --> 00:01:06,528
- 远程跳闸TJ1和TJ2
- 26
- 00:01:06,528 --> 00:01:10,321
- 保护跳闸入口可接入两套独立的微机保护
- 27
- 00:01:10,322 --> 00:01:12,282
- 或者其他保护继电器
- 28
- 00:01:12,282 --> 00:01:15,292
- 有的也会接入两套独立的跳闸线圈
- 29
- 00:01:15,292 --> 00:01:17,175
- 用于需要跳闸时的跳闸
- 30
- 00:01:17,175 --> 00:01:20,842
- 其中微机保护中的设置保护参数需一致
- 31
- 00:01:20,842 --> 00:01:20,843
- 32
- 00:01:20,843 --> 00:01:23,482
- 3:该线路具备防跳跃功能
- 33
- 00:01:23,482 --> 00:01:26,668
- TBJV继电器在断路器分闸时吸合
- 34
- 00:01:26,668 --> 00:01:29,598
- 通过它的辅助触点串入合闸回路
- 35
- 00:01:29,598 --> 00:01:33,642
- 防止在跳闸过程中又有合闸命令而损坏机构
- 36
- 00:01:33,642 --> 00:01:33,643
- 37
- 00:01:33,643 --> 00:01:37,752
- 4:KKJ是合后继电器也称磁保持继电器
- 38
- 00:01:37,752 --> 00:01:38,612
- 通过D1、
- 39
- 00:01:38,612 --> 00:01:42,932
- D2两个二极管的单相导通性能来保证只有手动合闸
- 40
- 00:01:42,932 --> 00:01:44,162
- 才能让其动作
- 41
- 00:01:44,162 --> 00:01:46,072
- 动作后不自动返回
- 42
- 00:01:46,072 --> 00:01:49,632
- 手动跳闸或者自动合闸后才能让其复归
- 43
- 00:01:49,642 --> 00:01:52,055
- 其接点可以用于重合闸
- 44
- 00:01:52,056 --> 00:01:52,057
- 45
- 00:01:52,057 --> 00:01:56,366
- 5:HYI与TYJ是合闸和跳闸压力继电器
- 46
- 00:01:56,366 --> 00:01:58,696
- 接入断路器机构的气压接点
- 47
- 00:01:58,696 --> 00:02:02,116
- 在以六氟化硫为灭弧绝缘介质的开关中
- 48
- 00:02:02,116 --> 00:02:04,429
- 如果六氟化硫气体有泄露
- 49
- 00:02:04,429 --> 00:02:09,189
- 则当气体压力降至危及灭弧时该接点T1和T2导通
- 50
- 00:02:09,189 --> 00:02:10,849
- 将操作回路断开
- 51
- 00:02:10,856 --> 00:02:12,176
- 禁止操作
- 52
- 00:02:12,176 --> 00:02:12,177
- 53
- 00:02:12,177 --> 00:02:14,316
- 6:位置继电器HWJ
- 54
- 00:02:14,316 --> 00:02:16,706
- TWT的作用有两个
- 55
- 00:02:16,706 --> 00:02:18,789
- 一是显示当前开关位置
- 56
- 00:02:18,789 --> 00:02:21,736
- 二是监视跳、合线圈是否完好
- 57
- 00:02:21,736 --> 00:02:21,737
- 58
- 00:02:21,737 --> 00:02:24,526
- 7:控制电源采双电源系统
- 59
- 00:02:24,526 --> 00:02:26,166
- 利用JJ继电器
- 60
- 00:02:26,166 --> 00:02:28,562
- 当一号直流屏电源KM1
- 61
- 00:02:28,562 --> 00:02:32,176
- 失电后 自动切换到备用电源KM2
|