220kV变压器-有载修改后.srt 5.5 KB

123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184185186187188189190191192193194195196197198199200201202203204205206207208209210211212213214215216217218219220221222223224225226227228229230231232233234235236237238239240241242243244245246247248249250251252253254255256257258259260261262263264265266267268269270271272273274275276277278279280281282283284285286287288289290291292293294295296297298299300301302303304305306307308309310311312313314315316317318319320
  1. 1
  2. 00:00:00,000 --> 00:00:05,290
  3. 220千伏有载调压开关是一种可在空载和带负荷条件下
  4. 2
  5. 00:00:05,290 --> 00:00:08,826
  6. 无需停电即可调整变压器输出电压的装置
  7. 3
  8. 00:00:08,826 --> 00:00:12,496
  9. 通过分接头档位转换调节高压绕组匝数
  10. 4
  11. 00:00:12,496 --> 00:00:14,166
  12. 从而改变负荷侧电压
  13. 5
  14. 00:00:14,720 --> 00:00:17,250
  15. 由于越靠近中性点电压越低
  16. 6
  17. 00:00:17,250 --> 00:00:20,300
  18. 该调压开关通过改变中性点匝数
  19. 7
  20. 00:00:20,300 --> 00:00:22,013
  21. 以及通过范围开关
  22. 8
  23. 00:00:22,013 --> 00:00:23,613
  24. 选择线圈方向
  25. 9
  26. 00:00:23,613 --> 00:00:25,153
  27. 加位或者减位
  28. 10
  29. 00:00:25,153 --> 00:00:26,813
  30. 来转换电流方向
  31. 11
  32. 00:00:26,813 --> 00:00:29,013
  33. 选择增大或者抵消磁场
  34. 12
  35. 00:00:29,013 --> 00:00:31,346
  36. 使调节倍数增加一倍
  37. 13
  38. 00:00:31,347 --> 00:00:34,027
  39. 它分为操作系统和执行系统
  40. 14
  41. 00:00:34,027 --> 00:00:37,587
  42. 操作系统通过电机或手动转动提供动力
  43. 15
  44. 00:00:37,587 --> 00:00:40,307
  45. 执行机构用于切换绕组匝数
  46. 16
  47. 00:00:40,307 --> 00:00:44,040
  48. 其中执行机构由选择开关和切换开关组成
  49. 17
  50. 00:00:44,040 --> 00:00:47,790
  51. 选择开关连接各个调节的不同匝数的绕组
  52. 18
  53. 00:00:47,790 --> 00:00:49,500
  54. 分别为1-8号抽头
  55. 19
  56. 00:00:50,067 --> 00:00:53,427
  57. 在三相系统中 每相又分为两层
  58. 20
  59. 00:00:57,652 --> 00:01:02,097
  60. 上层为奇数1357抽头抽头及范围开关共用触头
  61. 21
  62. 00:01:02,097 --> 00:01:06,467
  63. 下层为偶数2468号抽头和一个范围开关共用抽头
  64. 22
  65. 00:01:06,467 --> 00:01:09,767
  66. 用于选择需调节的绕组和绕组的方向
  67. 23
  68. 00:01:09,767 --> 00:01:12,317
  69. 也用于预选需要转换的匝数
  70. 24
  71. 00:01:12,317 --> 00:01:14,427
  72. 切换开关主要是选择的匝数
  73. 25
  74. 00:01:14,987 --> 00:01:17,160
  75. 每相绕组有4个触头
  76. 26
  77. 00:01:17,160 --> 00:01:21,227
  78. 分别为A1到A4
  79. 27
  80. 00:01:21,227 --> 00:01:24,667
  81. B1到B4
  82. 28
  83. 00:01:24,667 --> 00:01:26,187
  84. C1到C4
  85. 29
  86. 00:01:26,187 --> 00:01:28,880
  87. 总计12个触头
  88. 30
  89. 00:01:28,880 --> 00:01:35,760
  90. 通过步进方式 让一组或两组触头接通
  91. 31
  92. 00:01:35,761 --> 00:01:37,547
  93. 中间经过渡电阻
  94. 32
  95. 00:01:37,547 --> 00:01:45,934
  96. 顺利切换到预选匝数 后经中性点线排回到变压器中性点
  97. 33
  98. 00:01:45,935 --> 00:01:49,255
  99. 接下来让我们演示一下它的操作方法
  100. 34
  101. 00:01:49,255 --> 00:01:51,085
  102. 假设我们现在为一档
  103. 35
  104. 00:01:51,085 --> 00:01:52,795
  105. 想降低负载电压
  106. 36
  107. 00:01:52,795 --> 00:01:54,065
  108. 调节到二档
  109. 37
  110. 00:01:54,065 --> 00:01:55,935
  111. 由于遵循抵挡绕组少
  112. 38
  113. 00:01:55,935 --> 00:01:57,415
  114. 高档绕组多
  115. 39
  116. 00:01:57,415 --> 00:02:00,385
  117. 那么此时范围开关是在加档位置
  118. 40
  119. 00:02:00,385 --> 00:02:03,515
  120. 而选择开关绕组在 上层1号抽头位置
  121. 41
  122. 00:02:04,069 --> 00:02:09,615
  123. 我们手动摇动转动或者电机转动 经竖轴运动 横轴运动
  124. 42
  125. 00:02:09,616 --> 00:02:12,916
  126. 带动调压开关的选择开关的主轴运动
  127. 43
  128. 00:02:12,916 --> 00:02:14,316
  129. 经旋转齿盘
  130. 44
  131. 00:02:14,316 --> 00:02:17,096
  132. 拨动下端选择开关齿盘主轴运动
  133. 45
  134. 00:02:17,096 --> 00:02:20,322
  135. 让预选连接上层2号抽头绕组
  136. 46
  137. 00:02:20,323 --> 00:02:23,723
  138. 同时上端主轴带动切换开关快慢机
  139. 47
  140. 00:02:23,723 --> 00:02:27,193
  141. 使得触头中间的尾推弹簧机构有节奏的运动
  142. 48
  143. 00:02:27,750 --> 00:02:32,590
  144. 现在面临的情况是电经过下方分接开关1号绕组连接
  145. 49
  146. 00:02:32,590 --> 00:02:35,830
  147. 切换开关中的A1触头到达中性点
  148. 50
  149. 00:02:35,830 --> 00:02:42,176
  150. 分接开关2号绕组连接
  151. 51
  152. 00:02:42,177 --> 00:02:44,617
  153. 切换开关中的A4触头上
  154. 52
  155. 00:02:44,617 --> 00:02:48,137
  156. 首先连接A2
  157. 53
  158. 00:02:48,137 --> 00:02:54,083
  159. 然后断开A1触头
  160. 54
  161. 00:02:54,084 --> 00:02:55,670
  162. 接通A3触头
  163. 55
  164. 00:02:55,670 --> 00:02:59,217
  165. 断开A2触头
  166. 56
  167. 00:02:59,217 --> 00:03:02,977
  168. 连接第A4触头
  169. 57
  170. 00:03:02,977 --> 00:03:08,617
  171. 断开A3触头
  172. 58
  173. 00:03:08,618 --> 00:03:11,524
  174. 此时电经过分接开关2号绕组
  175. 59
  176. 00:03:11,524 --> 00:03:19,151
  177. 经过切换开关中的A4触头到达中性点
  178. 60
  179. 00:03:19,152 --> 00:03:21,952
  180. 这就是变压器经有载调压开关
  181. 61
  182. 00:03:21,952 --> 00:03:24,312
  183. 顺利从一档调节到二档的位置
  184. 62
  185. 00:03:24,872 --> 00:03:26,242
  186. 需要注意的是
  187. 63
  188. 00:03:26,242 --> 00:03:29,192
  189. 有载调压开关是不能跳档调节的
  190. 64
  191. 00:03:29,192 --> 00:03:30,952
  192. 只逐步一档一档调节
  193. 65
  194. 00:03:30,952 --> 00:03:34,178
  195. 当八档到九档时情况会比较特殊
  196. 66
  197. 00:03:34,179 --> 00:03:37,589
  198. 9档分为9A、9B和9C共三档
  199. 67
  200. 00:03:37,589 --> 00:03:40,109
  201. 9B为极性转换的标准档位
  202. 68
  203. 00:03:40,109 --> 00:03:41,285
  204. 可长期运转
  205. 69
  206. 00:03:41,285 --> 00:03:46,379
  207. 9A、9C为过渡档位 只可临时运行不可长期运行
  208. 70
  209. 00:03:46,379 --> 00:03:48,559
  210. 这就顺利的从加档位置
  211. 71
  212. 00:03:48,559 --> 00:03:50,369
  213. 切换到了减档位置
  214. 72
  215. 00:03:50,369 --> 00:03:52,912
  216. 从十档开始直至加到十七档
  217. 73
  218. 00:03:52,912 --> 00:03:56,352
  219. 其过程是1号绕组到8号绕组的切换
  220. 74
  221. 00:03:56,352 --> 00:03:59,052
  222. 从而完成1-17档的加档过程
  223. 75
  224. 00:03:59,059 --> 00:04:01,392
  225. 以实现负载的降压过程
  226. 76
  227. 00:04:01,393 --> 00:04:03,413
  228. 而减档责恰恰相反
  229. 77
  230. 00:04:03,413 --> 00:04:05,583
  231. 通过手动或电机反转
  232. 78
  233. 00:04:05,583 --> 00:04:08,633
  234. 下面为17档切换至1档的运动状态
  235. 79
  236. 00:04:08,633 --> 00:04:13,859
  237. 从而完成17-1档的减档过程 以实现负载的电压升高
  238. 80