| 123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104 |
- 1
- 00:00:00,000 --> 00:00:02,490
- KK是手自动分合闸旋钮
- 2
- 00:00:02,490 --> 00:00:04,870
- 用于手动本地控制分合闸
- 3
- 00:00:04,870 --> 00:00:09,610
- 自动远程控制用于远程操作箱或自动化控制或国网平台
- 4
- 00:00:09,610 --> 00:00:10,560
- 远程入口
- 5
- 00:00:10,560 --> 00:00:12,770
- 旋钮打到手动控制时
- 6
- 00:00:12,770 --> 00:00:14,840
- 101和103接通
- 7
- 00:00:14,840 --> 00:00:16,390
- 按动合闸按钮HA
- 8
- 00:00:16,390 --> 00:00:19,130
- 接通 103 和 105
- 9
- 00:00:19,130 --> 00:00:24,050
- 105的线通过航空插头到达真空断路器VS1的常闭点
- 10
- 00:00:24,053 --> 00:00:28,733
- 该常闭点用于防止断路器处于合闸状态时再次合闸
- 11
- 00:00:28,733 --> 00:00:30,383
- 接到合闸电磁铁
- 12
- 00:00:30,386 --> 00:00:33,096
- 合闸电磁铁得电吸合用于合闸
- 13
- 00:00:33,096 --> 00:00:34,946
- 当按动分闸按钮时
- 14
- 00:00:34,946 --> 00:00:36,106
- 133得电
- 15
- 00:00:36,106 --> 00:00:39,240
- 通过航空插头到达断路器常开触点
- 16
- 00:00:39,240 --> 00:00:43,010
- 该常开触点用于防止分闸状态时再次分闸
- 17
- 00:00:43,010 --> 00:00:44,720
- 接通分闸电磁铁
- 18
- 00:00:44,720 --> 00:00:45,620
- 用于分闸
- 19
- 00:00:45,626 --> 00:00:47,666
- 当切换到远程控制时
- 20
- 00:00:47,666 --> 00:00:49,086
- 13号线接通
- 21
- 00:00:49,086 --> 00:00:51,933
- 通过远程操作箱或者国网平台
- 22
- 00:00:51,933 --> 00:00:55,443
- 或者自动化PLC DCS 等控制分合闸
- 23
- 00:00:55,443 --> 00:00:56,798
- 合闸指示灯HG
- 24
- 00:00:56,798 --> 00:01:00,853
- 通过连接一个真空断路器的常开点用于指示合闸
- 25
- 00:01:00,853 --> 00:01:04,643
- 分闸指示灯HR连接一个真空断路器的常闭点
- 26
- 00:01:04,643 --> 00:01:05,993
- 用于指示分闸
|