10kV真空断路器二次原理VS1二次线路图解析.srt 1.7 KB

123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104
  1. 1
  2. 00:00:00,000 --> 00:00:02,490
  3. KK是手自动分合闸旋钮
  4. 2
  5. 00:00:02,490 --> 00:00:04,870
  6. 用于手动本地控制分合闸
  7. 3
  8. 00:00:04,870 --> 00:00:09,610
  9. 自动远程控制用于远程操作箱或自动化控制或国网平台
  10. 4
  11. 00:00:09,610 --> 00:00:10,560
  12. 远程入口
  13. 5
  14. 00:00:10,560 --> 00:00:12,770
  15. 旋钮打到手动控制时
  16. 6
  17. 00:00:12,770 --> 00:00:14,840
  18. 101和103接通
  19. 7
  20. 00:00:14,840 --> 00:00:16,390
  21. 按动合闸按钮HA
  22. 8
  23. 00:00:16,390 --> 00:00:19,130
  24. 接通 103 和 105
  25. 9
  26. 00:00:19,130 --> 00:00:24,050
  27. 105的线通过航空插头到达真空断路器VS1的常闭点
  28. 10
  29. 00:00:24,053 --> 00:00:28,733
  30. 该常闭点用于防止断路器处于合闸状态时再次合闸
  31. 11
  32. 00:00:28,733 --> 00:00:30,383
  33. 接到合闸电磁铁
  34. 12
  35. 00:00:30,386 --> 00:00:33,096
  36. 合闸电磁铁得电吸合用于合闸
  37. 13
  38. 00:00:33,096 --> 00:00:34,946
  39. 当按动分闸按钮时
  40. 14
  41. 00:00:34,946 --> 00:00:36,106
  42. 133得电
  43. 15
  44. 00:00:36,106 --> 00:00:39,240
  45. 通过航空插头到达断路器常开触点
  46. 16
  47. 00:00:39,240 --> 00:00:43,010
  48. 该常开触点用于防止分闸状态时再次分闸
  49. 17
  50. 00:00:43,010 --> 00:00:44,720
  51. 接通分闸电磁铁
  52. 18
  53. 00:00:44,720 --> 00:00:45,620
  54. 用于分闸
  55. 19
  56. 00:00:45,626 --> 00:00:47,666
  57. 当切换到远程控制时
  58. 20
  59. 00:00:47,666 --> 00:00:49,086
  60. 13号线接通
  61. 21
  62. 00:00:49,086 --> 00:00:51,933
  63. 通过远程操作箱或者国网平台
  64. 22
  65. 00:00:51,933 --> 00:00:55,443
  66. 或者自动化PLC DCS 等控制分合闸
  67. 23
  68. 00:00:55,443 --> 00:00:56,798
  69. 合闸指示灯HG
  70. 24
  71. 00:00:56,798 --> 00:01:00,853
  72. 通过连接一个真空断路器的常开点用于指示合闸
  73. 25
  74. 00:01:00,853 --> 00:01:04,643
  75. 分闸指示灯HR连接一个真空断路器的常闭点
  76. 26
  77. 00:01:04,643 --> 00:01:05,993
  78. 用于指示分闸