| 123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184185186187188189190191192193194195196197198199200201202203204205206207208209210211212213214215216217218219220221222223224225226227228229230231232233234235236237238239240241242243244 |
- 1
- 00:00:00,000 --> 00:00:02,930
- KYN28柜属于中置式开关柜
- 2
- 00:00:02,930 --> 00:00:05,400
- 该型开关柜主要用于10kV
- 3
- 00:00:05,400 --> 00:00:08,360
- 6kV等电力系统的电能分配与控制
- 4
- 00:00:08,360 --> 00:00:10,245
- 通过金属板材拼接
- 5
- 00:00:10,245 --> 00:00:11,350
- 将低压室
- 6
- 00:00:11,350 --> 00:00:12,415
- 断路器式
- 7
- 00:00:12,415 --> 00:00:13,345
- 母线室
- 8
- 00:00:13,345 --> 00:00:14,775
- 电缆式等隔离
- 9
- 00:00:14,775 --> 00:00:15,893
- 模块化设计
- 10
- 00:00:15,893 --> 00:00:18,333
- 确保了各功能区互不干扰
- 11
- 00:00:18,334 --> 00:00:21,609
- 操作系统和智能组合电气可灵活搭配
- 12
- 00:00:21,609 --> 00:00:22,734
- 实现操控
- 13
- 00:00:22,734 --> 00:00:23,514
- 检测
- 14
- 00:00:23,514 --> 00:00:24,600
- 保护等功能
- 15
- 00:00:24,600 --> 00:00:28,560
- 通过高压断路器实现电路的接通、分断及保护
- 16
- 00:00:28,561 --> 00:00:30,516
- 并且派生出了计量柜
- 17
- 00:00:30,516 --> 00:00:31,386
- PT柜
- 18
- 00:00:31,386 --> 00:00:32,431
- 进线柜等
- 19
- 00:00:32,431 --> 00:00:35,614
- 组合后让其成为整套高压柜的不二之选
- 20
- 00:00:35,614 --> 00:00:37,624
- 相较于固定式开关柜
- 21
- 00:00:37,624 --> 00:00:39,789
- 采用小车式断路器结构
- 22
- 00:00:39,789 --> 00:00:41,667
- 便于设备的维护与更换
- 23
- 00:00:41,667 --> 00:00:44,472
- 提升了操作灵活性和检修效率
- 24
- 00:00:44,472 --> 00:00:46,662
- 五防连锁机构的可靠设计
- 25
- 00:00:46,662 --> 00:00:48,552
- 也保证了设备和人员的安全
- 26
- 00:00:49,095 --> 00:00:51,268
- 现在模拟一下他的操控
- 27
- 00:00:51,268 --> 00:00:53,441
- 检修位置到试验位置
- 28
- 00:00:53,441 --> 00:00:56,335
- 首先将断路器放到移动手车上
- 29
- 00:00:56,335 --> 00:00:59,095
- 然后将手车调整到合适高度
- 30
- 00:00:59,095 --> 00:01:01,761
- 将手车插到连接控并锁死
- 31
- 00:01:01,762 --> 00:01:03,842
- 双手向里推动拉杆
- 32
- 00:01:03,842 --> 00:01:06,028
- 听到咔哒声后往里推
- 33
- 00:01:06,028 --> 00:01:07,962
- 缓慢将手车推入
- 34
- 00:01:07,962 --> 00:01:11,215
- 松开双手让手柄自复位卡进锁孔
- 35
- 00:01:11,215 --> 00:01:12,908
- 插上航空插头
- 36
- 00:01:12,908 --> 00:01:16,068
- 用手车摇把向里推动并缓慢摇动
- 37
- 00:01:16,069 --> 00:01:17,815
- 听到机械咔哒声
- 38
- 00:01:17,815 --> 00:01:19,535
- 并观察指示面板
- 39
- 00:01:19,535 --> 00:01:21,589
- 看到面板指示灯亮起
- 40
- 00:01:21,589 --> 00:01:23,469
- 说明到达实验位置
- 41
- 00:01:23,469 --> 00:01:25,802
- 实验位置到达工作位置
- 42
- 00:01:25,802 --> 00:01:28,269
- 首先需观查两个先决条件
- 43
- 00:01:28,269 --> 00:01:31,069
- 指示面板接地刀闸是否在合位
- 44
- 00:01:31,069 --> 00:01:33,389
- 如果合位需先分开刀闸
- 45
- 00:01:33,389 --> 00:01:35,669
- 观查断路器是否在分位
- 46
- 00:01:35,669 --> 00:01:37,069
- 如果在合位
- 47
- 00:01:37,069 --> 00:01:38,762
- 需先手动分闸
- 48
- 00:01:38,762 --> 00:01:40,215
- 满足条件后
- 49
- 00:01:40,216 --> 00:01:42,096
- 可以继续摇动摇把
- 50
- 00:01:42,096 --> 00:01:43,936
- 随着断路器往里进
- 51
- 00:01:43,936 --> 00:01:46,309
- 活门在底部杠杆下打开
- 52
- 00:01:46,310 --> 00:01:47,910
- 梅花插头进入
- 53
- 00:01:47,910 --> 00:01:49,656
- 直到一声咔哒声
- 54
- 00:01:49,656 --> 00:01:51,256
- 摇把明显卡顿
- 55
- 00:01:51,256 --> 00:01:52,110
- 摇不动
- 56
- 00:01:52,110 --> 00:01:54,683
- 指示面板显示进入工作位置
- 57
- 00:01:54,683 --> 00:01:56,256
- 说明到达位置
- 58
- 00:01:56,256 --> 00:01:58,163
- 摇动时如果摇不动
- 59
- 00:01:58,164 --> 00:01:59,444
- 则需停止
- 60
- 00:01:59,444 --> 00:02:01,804
- 检查机械结构是否卡顿
- 61
- 00:02:01,804 --> 00:02:04,417
- 然后再进行分合闸操作即可
|