10kV开关柜-机械特性.srt 3.4 KB

123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184185186187188189190191192193194195196197198199200201202203204205206207208209210211212213214215216217218219220221222223224225226227228
  1. 1
  2. 00:00:00,000 --> 00:00:03,100
  3. KYN28柜属于中置式开关柜
  4. 2
  5. 00:00:03,100 --> 00:00:05,710
  6. 该型开关柜主要用于10kV
  7. 3
  8. 00:00:05,710 --> 00:00:08,840
  9. 6kV等电力系统的电能分配与控制
  10. 4
  11. 00:00:08,840 --> 00:00:10,840
  12. 通过金属板材拼接
  13. 5
  14. 00:00:10,840 --> 00:00:12,010
  15. 将低压室
  16. 6
  17. 00:00:12,010 --> 00:00:13,140
  18. 断路器式
  19. 7
  20. 00:00:13,140 --> 00:00:14,120
  21. 母线室
  22. 8
  23. 00:00:14,120 --> 00:00:15,430
  24. 电缆式隔离
  25. 9
  26. 00:00:15,430 --> 00:00:16,580
  27. 模块化设计
  28. 10
  29. 00:00:16,586 --> 00:00:19,173
  30. 确保了各功能区互不干扰
  31. 11
  32. 00:00:19,174 --> 00:00:22,634
  33. 操作系统和智能组合电气可灵活搭配
  34. 12
  35. 00:00:22,634 --> 00:00:23,814
  36. 实现操控
  37. 13
  38. 00:00:23,814 --> 00:00:24,634
  39. 检测
  40. 14
  41. 00:00:24,634 --> 00:00:25,627
  42. 保护功能
  43. 15
  44. 00:00:25,627 --> 00:00:29,814
  45. 通过高压断路器实现电路的接通、分断及保护
  46. 16
  47. 00:00:29,814 --> 00:00:31,884
  48. 并且派生出了计量柜
  49. 17
  50. 00:00:31,884 --> 00:00:32,804
  51. PT柜
  52. 18
  53. 00:00:32,804 --> 00:00:33,914
  54. 进线柜等
  55. 19
  56. 00:00:33,914 --> 00:00:37,267
  57. 组合后让其成为整套高压柜的不二之选
  58. 20
  59. 00:00:37,267 --> 00:00:39,387
  60. 相较于固定式开关柜
  61. 21
  62. 00:00:39,387 --> 00:00:41,667
  63. 采用小车式断路器结构
  64. 22
  65. 00:00:41,667 --> 00:00:43,667
  66. 便于设备的维护与更换
  67. 23
  68. 00:00:43,667 --> 00:00:46,627
  69. 提升了操作灵活性和检修效率
  70. 24
  71. 00:00:46,627 --> 00:00:48,957
  72. 五防连锁机构的可靠设计
  73. 25
  74. 00:00:48,957 --> 00:00:50,957
  75. 也保证了设备和人员的安全
  76. 26
  77. 00:00:51,521 --> 00:00:53,801
  78. 检修位置到试验位置
  79. 27
  80. 00:00:53,801 --> 00:00:56,867
  81. 首先将断路器放到移动手车上
  82. 28
  83. 00:00:56,868 --> 00:00:59,788
  84. 然后将手车调整到合适高度
  85. 29
  86. 00:00:59,788 --> 00:01:02,614
  87. 将手车插到连接控并锁死
  88. 30
  89. 00:01:02,615 --> 00:01:04,748
  90. 双手向里推动拉杆
  91. 31
  92. 00:01:04,748 --> 00:01:07,055
  93. 听到咔哒声后往里推
  94. 32
  95. 00:01:07,055 --> 00:01:09,055
  96. 缓慢将手车推入
  97. 33
  98. 00:01:09,055 --> 00:01:12,468
  99. 松开双手让手柄自复位卡进锁孔
  100. 34
  101. 00:01:12,468 --> 00:01:14,255
  102. 插上航空插头
  103. 35
  104. 00:01:14,255 --> 00:01:16,495
  105. 用手车摇把缓慢摇动
  106. 36
  107. 00:01:16,495 --> 00:01:18,175
  108. 听到清脆响动
  109. 37
  110. 00:01:18,175 --> 00:01:19,988
  111. 并观察指示面板
  112. 38
  113. 00:01:19,988 --> 00:01:22,295
  114. 看到面板指示灯亮起
  115. 39
  116. 00:01:22,295 --> 00:01:24,281
  117. 说明到达实验位置
  118. 40
  119. 00:01:24,281 --> 00:01:26,748
  120. 实验位置到达工作位置
  121. 41
  122. 00:01:26,748 --> 00:01:29,175
  123. 首先观查两个先决条件
  124. 42
  125. 00:01:29,175 --> 00:01:32,135
  126. 指示面板接地刀闸是否在合位
  127. 43
  128. 00:01:32,135 --> 00:01:34,575
  129. 如果合位需先分开刀闸
  130. 44
  131. 00:01:34,575 --> 00:01:36,988
  132. 观查断路器是否在分位
  133. 45
  134. 00:01:36,988 --> 00:01:38,455
  135. 如果在合位
  136. 46
  137. 00:01:38,455 --> 00:01:40,255
  138. 需先手动分闸
  139. 47
  140. 00:01:40,255 --> 00:01:42,948
  141. 没问题就可以继续摇动摇把
  142. 48
  143. 00:01:42,948 --> 00:01:45,055
  144. 随着断路器往里进
  145. 49
  146. 00:01:45,055 --> 00:01:47,535
  147. 活门在底部杠杆下打开
  148. 50
  149. 00:01:47,535 --> 00:01:49,295
  150. 梅花插头进入
  151. 51
  152. 00:01:49,295 --> 00:01:51,095
  153. 直到一声卡巴声
  154. 52
  155. 00:01:51,095 --> 00:01:54,575
  156. 摇不动 指示面板显示进入工作位置
  157. 53
  158. 00:01:54,575 --> 00:01:56,241
  159. 说明到达位置
  160. 54
  161. 00:01:56,241 --> 00:01:58,401
  162. 摇动时如果摇不动
  163. 55
  164. 00:01:58,401 --> 00:01:59,575
  165. 则停止
  166. 56
  167. 00:01:59,575 --> 00:02:02,081
  168. 检查机械结构是否卡顿
  169. 57
  170. 00:02:02,082 --> 00:02:04,655
  171. 然后进行分合闸操作即可