| 123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184185186187188189190191192193194195196197198199200201202203204205206207208209210211212213214215216217218219220221222223224225226227228 |
- 1
- 00:00:00,000 --> 00:00:03,100
- KYN28柜属于中置式开关柜
- 2
- 00:00:03,100 --> 00:00:05,710
- 该型开关柜主要用于10kV
- 3
- 00:00:05,710 --> 00:00:08,840
- 6kV等电力系统的电能分配与控制
- 4
- 00:00:08,840 --> 00:00:10,840
- 通过金属板材拼接
- 5
- 00:00:10,840 --> 00:00:12,010
- 将低压室
- 6
- 00:00:12,010 --> 00:00:13,140
- 断路器式
- 7
- 00:00:13,140 --> 00:00:14,120
- 母线室
- 8
- 00:00:14,120 --> 00:00:15,430
- 电缆式隔离
- 9
- 00:00:15,430 --> 00:00:16,580
- 模块化设计
- 10
- 00:00:16,586 --> 00:00:19,173
- 确保了各功能区互不干扰
- 11
- 00:00:19,174 --> 00:00:22,634
- 操作系统和智能组合电气可灵活搭配
- 12
- 00:00:22,634 --> 00:00:23,814
- 实现操控
- 13
- 00:00:23,814 --> 00:00:24,634
- 检测
- 14
- 00:00:24,634 --> 00:00:25,627
- 保护功能
- 15
- 00:00:25,627 --> 00:00:29,814
- 通过高压断路器实现电路的接通、分断及保护
- 16
- 00:00:29,814 --> 00:00:31,884
- 并且派生出了计量柜
- 17
- 00:00:31,884 --> 00:00:32,804
- PT柜
- 18
- 00:00:32,804 --> 00:00:33,914
- 进线柜等
- 19
- 00:00:33,914 --> 00:00:37,267
- 组合后让其成为整套高压柜的不二之选
- 20
- 00:00:37,267 --> 00:00:39,387
- 相较于固定式开关柜
- 21
- 00:00:39,387 --> 00:00:41,667
- 采用小车式断路器结构
- 22
- 00:00:41,667 --> 00:00:43,667
- 便于设备的维护与更换
- 23
- 00:00:43,667 --> 00:00:46,627
- 提升了操作灵活性和检修效率
- 24
- 00:00:46,627 --> 00:00:48,957
- 五防连锁机构的可靠设计
- 25
- 00:00:48,957 --> 00:00:50,957
- 也保证了设备和人员的安全
- 26
- 00:00:51,521 --> 00:00:53,801
- 检修位置到试验位置
- 27
- 00:00:53,801 --> 00:00:56,867
- 首先将断路器放到移动手车上
- 28
- 00:00:56,868 --> 00:00:59,788
- 然后将手车调整到合适高度
- 29
- 00:00:59,788 --> 00:01:02,614
- 将手车插到连接控并锁死
- 30
- 00:01:02,615 --> 00:01:04,748
- 双手向里推动拉杆
- 31
- 00:01:04,748 --> 00:01:07,055
- 听到咔哒声后往里推
- 32
- 00:01:07,055 --> 00:01:09,055
- 缓慢将手车推入
- 33
- 00:01:09,055 --> 00:01:12,468
- 松开双手让手柄自复位卡进锁孔
- 34
- 00:01:12,468 --> 00:01:14,255
- 插上航空插头
- 35
- 00:01:14,255 --> 00:01:16,495
- 用手车摇把缓慢摇动
- 36
- 00:01:16,495 --> 00:01:18,175
- 听到清脆响动
- 37
- 00:01:18,175 --> 00:01:19,988
- 并观察指示面板
- 38
- 00:01:19,988 --> 00:01:22,295
- 看到面板指示灯亮起
- 39
- 00:01:22,295 --> 00:01:24,281
- 说明到达实验位置
- 40
- 00:01:24,281 --> 00:01:26,748
- 实验位置到达工作位置
- 41
- 00:01:26,748 --> 00:01:29,175
- 首先观查两个先决条件
- 42
- 00:01:29,175 --> 00:01:32,135
- 指示面板接地刀闸是否在合位
- 43
- 00:01:32,135 --> 00:01:34,575
- 如果合位需先分开刀闸
- 44
- 00:01:34,575 --> 00:01:36,988
- 观查断路器是否在分位
- 45
- 00:01:36,988 --> 00:01:38,455
- 如果在合位
- 46
- 00:01:38,455 --> 00:01:40,255
- 需先手动分闸
- 47
- 00:01:40,255 --> 00:01:42,948
- 没问题就可以继续摇动摇把
- 48
- 00:01:42,948 --> 00:01:45,055
- 随着断路器往里进
- 49
- 00:01:45,055 --> 00:01:47,535
- 活门在底部杠杆下打开
- 50
- 00:01:47,535 --> 00:01:49,295
- 梅花插头进入
- 51
- 00:01:49,295 --> 00:01:51,095
- 直到一声卡巴声
- 52
- 00:01:51,095 --> 00:01:54,575
- 摇不动 指示面板显示进入工作位置
- 53
- 00:01:54,575 --> 00:01:56,241
- 说明到达位置
- 54
- 00:01:56,241 --> 00:01:58,401
- 摇动时如果摇不动
- 55
- 00:01:58,401 --> 00:01:59,575
- 则停止
- 56
- 00:01:59,575 --> 00:02:02,081
- 检查机械结构是否卡顿
- 57
- 00:02:02,082 --> 00:02:04,655
- 然后进行分合闸操作即可
|