123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184
  1. 1
  2. 00:00:00,000 --> 00:00:03,660
  3. 1.该二次线路具备手动本地分合闸功能
  4. 2
  5. 00:00:03,660 --> 00:00:04,910
  6. 用于本地操作
  7. 3
  8. 00:00:04,910 --> 00:00:06,080
  9. 远程分合闸
  10. 4
  11. 00:00:06,080 --> 00:00:10,960
  12. 用于远程自动化或者国网平台或者远控箱分合闸功能
  13. 5
  14. 00:00:10,960 --> 00:00:14,250
  15. 当分合闸旋钮kk打到本地控制时
  16. 6
  17. 00:00:14,250 --> 00:00:15,910
  18. 可旋至手动合闸
  19. 7
  20. 00:00:15,910 --> 00:00:17,706
  21. 让KK1   2接通
  22. 8
  23. 00:00:17,706 --> 00:00:21,120
  24. 使合闸线圈HQ吸合 用于合闸
  25. 9
  26. 00:00:21,120 --> 00:00:27,480
  27. 当旋钮钮到分闸时 11   12端子接通 使分闸线圈TQ跳闸
  28. 10
  29. 00:00:27,480 --> 00:00:32,440
  30. 当选至远程时5      6端子接通 7      8端子接通
  31. 11
  32. 00:00:32,440 --> 00:00:35,780
  33. 可用远程合闸入口和远程分闸入口
  34. 12
  35. 00:00:35,780 --> 00:00:37,170
  36. 接到国网平台
  37. 13
  38. 00:00:37,170 --> 00:00:38,140
  39. 远控箱去
  40. 14
  41. 00:00:38,140 --> 00:00:40,093
  42. 去分合闸断路器
  43. 15
  44. 00:00:40,094 --> 00:00:43,664
  45. 2.该线路可通过接入微机综合保护器
  46. 16
  47. 00:00:43,664 --> 00:00:47,760
  48. 让其具备二次重合闸功能和远程跳闸功能
  49. 17
  50. 00:00:47,761 --> 00:00:50,871
  51. 来自微机保护器的重合闸常开点HJ
  52. 18
  53. 00:00:50,871 --> 00:00:52,631
  54. 可使意外跳闸时
  55. 19
  56. 00:00:52,631 --> 00:00:53,961
  57. 根据微保设置
  58. 20
  59. 00:00:53,961 --> 00:00:55,667
  60. 来一次重合闸
  61. 21
  62. 00:00:55,668 --> 00:00:57,548
  63. 当不想利用该功能时
  64. 22
  65. 00:00:57,548 --> 00:00:58,778
  66. 或者检修时
  67. 23
  68. 00:00:58,778 --> 00:01:00,458
  69. 可挑其保护连片
  70. 24
  71. 00:01:00,458 --> 00:01:04,681
  72. 远程跳闸TJ保护跳闸入口可接入微机保护
  73. 25
  74. 00:01:04,682 --> 00:01:09,388
  75. 或者其他保护继电器 用于需要跳闸时的跳闸
  76. 26
  77. 00:01:09,300 --> 00:01:11,468
  78. 3.该线路具备防跳跃功能
  79. 27
  80. 00:01:11,468 --> 00:01:14,655
  81. TBJV继电器在断路器分闸时吸合
  82. 28
  83. 00:01:14,655 --> 00:01:17,585
  84. 通过它的辅助触点串入合闸回路
  85. 29
  86. 00:01:17,585 --> 00:01:21,635
  87. 防止在跳闸过程中又有合闸命令而损坏机构
  88. 30
  89. 00:01:21,642 --> 00:01:25,752
  90. 4.KKJ是合后继电器也称磁保持继电器
  91. 31
  92. 00:01:25,752 --> 00:01:30,932
  93. 通过D1、D2两个二极管的单相导通性能来保证只有手动合闸
  94. 32
  95. 00:01:30,932 --> 00:01:32,162
  96. 才能让其动作
  97. 33
  98. 00:01:32,162 --> 00:01:34,072
  99. 动作后不自动返回
  100. 34
  101. 00:01:34,072 --> 00:01:37,632
  102. 手动跳闸或者自动合闸后才能让其复归
  103. 35
  104. 00:01:37,642 --> 00:01:40,055
  105. 其接点可以用于重合闸
  106. 36
  107. 00:01:40,056 --> 00:01:44,366
  108. 5.HYI与TYJ是合闸和跳闸压力继电器
  109. 37
  110. 00:01:44,366 --> 00:01:46,696
  111. 接入断路器机构的气压接点
  112. 38
  113. 00:01:46,696 --> 00:01:50,116
  114. 在以六氟化硫为灭弧绝缘介质的开关中
  115. 39
  116. 00:01:50,116 --> 00:01:52,429
  117. 如果六氟化硫气体有泄露
  118. 40
  119. 00:01:52,429 --> 00:01:57,189
  120. 则当气体压力降至危及灭弧时该接点T1和T2导通
  121. 41
  122. 00:01:57,189 --> 00:01:58,849
  123. 将操作回路断开
  124. 42
  125. 00:01:58,856 --> 00:02:00,176
  126. 禁止操作
  127. 43
  128. 00:02:00,176 --> 00:02:02,316
  129. 6.位置继电器HWJ
  130. 44
  131. 00:02:02,316 --> 00:02:04,706
  132. TWT的作用有两个
  133. 45
  134. 00:02:04,706 --> 00:02:06,789
  135. 一是显示当前开关位置
  136. 46