1 00:00:00,000 --> 00:00:03,660 1:该二次线路具备手动本地分合闸功能 2 00:00:03,660 --> 00:00:04,910 用于本地操作 3 00:00:04,910 --> 00:00:06,080 远程分合闸 4 00:00:06,080 --> 00:00:10,960 用于远程自动化或者国网平台或者远控箱分合闸功能 5 00:00:10,960 --> 00:00:14,250 当分合闸旋钮kk打到本地控制时 6 00:00:14,250 --> 00:00:15,910 可旋至手动合闸 7 00:00:15,910 --> 00:00:17,706 让KK1   2接通 8 00:00:17,706 --> 00:00:21,120 使合闸线圈HQ吸合 用于合闸 9 00:00:21,120 --> 00:00:27,480 当旋钮钮到分闸时 11   12端子接通 使分闸线圈TQ跳闸 10 00:00:27,480 --> 00:00:32,440 当选至远程时5      6端子接通 7      8端子接通 11 00:00:32,440 --> 00:00:35,780 可用远程合闸入口和远程分闸入口 12 00:00:35,780 --> 00:00:37,170 接到国网平台 13 00:00:37,170 --> 00:00:38,140 远控箱去 14 00:00:38,140 --> 00:00:40,093 去分合闸断路器 15 00:00:40,094 -->00:00:40,095 16 00:00:40,095 --> 00:00:43,664 2:该线路可通过接入微机综合保护器 17 00:00:43,664 --> 00:00:46,724 让其具备两套独立的二次重合闸功能 18 00:00:46,724 --> 00:00:49,534 和两套独立的远程跳闸功能 19 00:00:49,534 --> 00:00:54,944 来自两套独立的微机保护器的重合闸常开点HJ1和HJ2 20 00:00:54,944 --> 00:00:56,494 可使意外跳闸时 21 00:00:56,494 --> 00:00:59,507 根据微保设置 来一次重合闸 22 00:00:59,508 --> 00:01:01,368 当不想利用该功能时 23 00:01:01,368 --> 00:01:02,598 或者检修时 24 00:01:02,598 --> 00:01:04,298 可挑其保护连片 25 00:01:04,298 --> 00:01:06,528 远程跳闸TJ1和TJ2 26 00:01:06,528 --> 00:01:10,321 保护跳闸入口可接入两套独立的微机保护 27 00:01:10,322 --> 00:01:12,282 或者其他保护继电器 28 00:01:12,282 --> 00:01:15,292 有的也会接入两套独立的跳闸线圈 29 00:01:15,292 --> 00:01:17,175 用于需要跳闸时的跳闸 30 00:01:17,175 --> 00:01:20,842 其中微机保护中的设置保护参数需一致 31 00:01:20,842 --> 00:01:20,843 32 00:01:20,843 --> 00:01:23,482 3:该线路具备防跳跃功能 33 00:01:23,482 --> 00:01:26,668 TBJV继电器在断路器分闸时吸合 34 00:01:26,668 --> 00:01:29,598 通过它的辅助触点串入合闸回路 35 00:01:29,598 --> 00:01:33,642 防止在跳闸过程中又有合闸命令而损坏机构 36 00:01:33,642 --> 00:01:33,643 37 00:01:33,643 --> 00:01:37,752 4:KKJ是合后继电器也称磁保持继电器 38 00:01:37,752 --> 00:01:38,612 通过D1、 39 00:01:38,612 --> 00:01:42,932 D2两个二极管的单相导通性能来保证只有手动合闸 40 00:01:42,932 --> 00:01:44,162 才能让其动作 41 00:01:44,162 --> 00:01:46,072 动作后不自动返回 42 00:01:46,072 --> 00:01:49,632 手动跳闸或者自动合闸后才能让其复归 43 00:01:49,642 --> 00:01:52,055 其接点可以用于重合闸 44 00:01:52,056 --> 00:01:52,057 45 00:01:52,057 --> 00:01:56,366 5:HYI与TYJ是合闸和跳闸压力继电器 46 00:01:56,366 --> 00:01:58,696 接入断路器机构的气压接点 47 00:01:58,696 --> 00:02:02,116 在以六氟化硫为灭弧绝缘介质的开关中 48 00:02:02,116 --> 00:02:04,429 如果六氟化硫气体有泄露 49 00:02:04,429 --> 00:02:09,189 则当气体压力降至危及灭弧时该接点T1和T2导通 50 00:02:09,189 --> 00:02:10,849 将操作回路断开 51 00:02:10,856 --> 00:02:12,176 禁止操作 52 00:02:12,176 --> 00:02:12,177 53 00:02:12,177 --> 00:02:14,316 6:位置继电器HWJ 54 00:02:14,316 --> 00:02:16,706 TWT的作用有两个 55 00:02:16,706 --> 00:02:18,789 一是显示当前开关位置 56 00:02:18,789 --> 00:02:21,736 二是监视跳、合线圈是否完好 57 00:02:21,736 --> 00:02:21,737 58 00:02:21,737 --> 00:02:24,526 7:控制电源采双电源系统 59 00:02:24,526 --> 00:02:26,166 利用JJ继电器 60 00:02:26,166 --> 00:02:28,562 当一号直流屏电源KM1 61 00:02:28,562 --> 00:02:32,176 失电后 自动切换到备用电源KM2