1 00:00:00,000 --> 00:00:02,680 真空断路器机械联动特性 2 00:00:02,680 --> 00:00:08,133 储能机械:外部直流屏电源直流+220V经柜顶小母线 3 00:00:08,134 --> 00:00:12,094 到达低压室QF2 开关下因到端子排 4 00:00:12,094 --> 00:00:15,174 端子排到达转换开关航空插头 5 00:00:15,174 --> 00:00:18,174 到储能开关限位开关常闭点 6 00:00:18,174 --> 00:00:20,840 到直流储能电机+端子 7 00:00:20,841 --> 00:00:25,271 后经直流电机负端子到达储能限位开关常闭点后 8 00:00:25,271 --> 00:00:27,311 经航空插头出回到端子排 9 00:00:27,868 --> 00:00:30,534 后回到开关到柜顶小母线 10 00:00:30,534 --> 00:00:34,374 这样可手动或自动接通未储能电机让其转动 11 00:00:34,374 --> 00:00:36,384 经链条带动曲轴旋转 12 00:00:36,388 --> 00:00:39,241 带动合闸储能弹簧拉伸储能 13 00:00:39,242 --> 00:00:43,602 合闸机械 按动合闸按钮让合闸电磁铁吸合 14 00:00:43,602 --> 00:00:47,575 铁芯推动卡簧 或者手动按动合闸按钮 15 00:00:47,576 --> 00:00:50,949 推动卡簧 让合闸储能弹簧释放 16 00:00:50,949 --> 00:00:52,669 带动主轴旋转 17 00:00:52,669 --> 00:00:56,849 主轴后面有杠杆推动真空断路器动触头向上运动 18 00:00:56,849 --> 00:00:57,989 动静触头结合 19 00:00:58,550 --> 00:00:59,600 分闸机械 20 00:00:59,600 --> 00:01:00,650 在合闸时 21 00:01:00,650 --> 00:01:03,640 主轴运动带动三个分闸储能弹簧拉伸 22 00:01:04,190 --> 00:01:09,590 分闸弹簧已经储能 让按动分闸按钮让分闸电磁铁吸合 23 00:01:09,590 --> 00:01:13,630 铁芯推动卡簧释放 在分闸弹簧的能量下 24 00:01:13,630 --> 00:01:15,970 主轴旋转拉伸后面的连杆 25 00:01:15,970 --> 00:01:17,970 带动动触头往下运动 26 00:01:17,970 --> 00:01:19,830 使动静触头分开