1 00:00:00,000 --> 00:00:05,755 220千伏LW25断路器采用三相分体单端口结构 2 00:00:05,755 --> 00:00:08,026 每个产品由三个单极结构 3 00:00:08,026 --> 00:00:09,261 操作简单 4 00:00:09,261 --> 00:00:10,641 可单极操作 5 00:00:10,641 --> 00:00:12,531 也可三极一起操作 6 00:00:12,531 --> 00:00:14,281 便于安装和操作 7 00:00:14,281 --> 00:00:15,240 是变电站 8 00:00:15,240 --> 00:00:19,400 发电厂 以及输电线路理想的高压设备 9 00:00:19,400 --> 00:00:23,030 其具有优异的热稳定性和机械耐久性 10 00:00:23,030 --> 00:00:26,330 能够在恶劣的工作环境中长时间稳定运行 11 00:00:26,854 --> 00:00:28,204 断路器储能 12 00:00:28,204 --> 00:00:30,144 通过储能电机旋转 13 00:00:30,144 --> 00:00:33,534 电机齿轮联动两个棘爪交替偏心运动 14 00:00:33,534 --> 00:00:35,124 联动拉动滚轮 15 00:00:35,124 --> 00:00:37,139 带动竖轴向上运动 16 00:00:37,139 --> 00:00:39,944 带动合闸弹簧压缩变短从而储能 17 00:00:40,481 --> 00:00:42,491 合闸弹簧系统独立 18 00:00:42,491 --> 00:00:43,691 操作稳定 19 00:00:43,691 --> 00:00:45,136 合闸操作时 20 00:00:45,136 --> 00:00:46,571 电磁铁吸合 21 00:00:46,571 --> 00:00:48,067 铁芯向上运动 22 00:00:48,067 --> 00:00:49,727 带动闸锁旋转 23 00:00:49,727 --> 00:00:51,412 从而释放滚轮 24 00:00:51,412 --> 00:00:54,432 合闸弹簧在储存的能量下变长 25 00:00:54,432 --> 00:00:55,852 滚轮开始运动 26 00:00:55,867 --> 00:00:59,197 同时轴凸轮撞击连杆逆时针运动 27 00:00:59,197 --> 00:01:00,802 使杆向下运动 28 00:01:00,802 --> 00:01:05,481 同时拉动分闸储能杆向上运动对分闸弹簧进行储能 29 00:01:05,481 --> 00:01:07,711 带动拐臂顺时针旋转 30 00:01:07,711 --> 00:01:09,356 拉杆向前运动 31 00:01:09,356 --> 00:01:13,107 带动拐臂顺时针旋转拉动触头杆向上运动 32 00:01:13,107 --> 00:01:15,587 插入静触头完成合闸 33 00:01:15,588 --> 00:01:16,473 分闸 34 00:01:16,473 --> 00:01:18,908 分闸电磁铁得电并吸合 35 00:01:18,908 --> 00:01:20,598 铁芯向上运动 36 00:01:20,598 --> 00:01:22,203 推动分闸掣子 37 00:01:22,203 --> 00:01:23,734 压到触发联动杆 38 00:01:23,734 --> 00:01:26,369 触发联动杆撞击锁死机构 39 00:01:26,369 --> 00:01:28,524 使主轴顺时针旋转 40 00:01:28,524 --> 00:01:30,214 释放对主轴的束缚 41 00:01:30,214 --> 00:01:33,254 联动机构输出拐臂顺时针旋转 42 00:01:33,254 --> 00:01:35,289 推动竖轴向下运动 43 00:01:35,289 --> 00:01:37,459 分闸弹簧释放能量变长 44 00:01:37,468 --> 00:01:38,853 轴向上运动 45 00:01:38,853 --> 00:01:41,118 拉动拐臂逆时针旋转 46 00:01:41,118 --> 00:01:42,798 拉杆向后运动 47 00:01:42,798 --> 00:01:44,774 拉动拐臂逆时针旋转 48 00:01:44,774 --> 00:01:49,041 使动触头杆向下运动脱离静触点完成分闸 49 00:01:49,042 --> 00:01:53,787 此断路器可安全通过5000次不间断的机械寿命试验 50 00:01:53,787 --> 00:01:55,348 操作可靠性高 51 00:01:55,349 --> 00:01:57,289 无漏油、漏气风险 52 00:01:57,289 --> 00:02:01,199 且断路器本体与操作机构采用直接连接 53 00:02:01,199 --> 00:02:03,482 使得它体积小、重量轻 54 00:02:03,483 --> 00:02:05,813 高可靠的弹簧操动机构 55 00:02:05,813 --> 00:02:07,678 使结构简单清晰 56 00:02:07,678 --> 00:02:10,069 产品运行维护工作量很少 57 00:02:10,069 --> 00:02:14,856 只需定期查看六氟化硫气体表压和涂抹润滑脂即可