1 00:00:00,000 --> 00:00:02,490 KK是手自动分合闸旋钮 2 00:00:02,490 --> 00:00:04,870 用于手动本地控制分合闸 3 00:00:04,870 --> 00:00:09,610 自动远程控制用于远程操作箱或自动化控制或国网平台 4 00:00:09,610 --> 00:00:10,560 远程入口 5 00:00:10,560 --> 00:00:12,770 旋钮打到手动控制时 6 00:00:12,770 --> 00:00:14,840 101和103接通 7 00:00:14,840 --> 00:00:16,390 按动合闸按钮HA 8 00:00:16,390 --> 00:00:19,130 接通 103 和 105 9 00:00:19,130 --> 00:00:24,050 105的线通过航空插头到达真空断路器VS1的常闭点 10 00:00:24,053 --> 00:00:28,733 该常闭点用于防止断路器处于合闸状态时再次合闸 11 00:00:28,733 --> 00:00:30,383 接到合闸电磁铁 12 00:00:30,386 --> 00:00:33,096 合闸电磁铁得电吸合用于合闸 13 00:00:33,096 --> 00:00:34,946 当按动分闸按钮时 14 00:00:34,946 --> 00:00:36,106 133得电 15 00:00:36,106 --> 00:00:39,240 通过航空插头到达断路器常开触点 16 00:00:39,240 --> 00:00:43,010 该常开触点用于防止分闸状态时再次分闸 17 00:00:43,010 --> 00:00:44,720 接通分闸电磁铁 18 00:00:44,720 --> 00:00:45,620 用于分闸 19 00:00:45,626 --> 00:00:47,666 当切换到远程控制时 20 00:00:47,666 --> 00:00:49,086 13号线接通 21 00:00:49,086 --> 00:00:51,933 通过远程操作箱或者国网平台 22 00:00:51,933 --> 00:00:55,443 或者自动化PLC DCS 等控制分合闸 23 00:00:55,443 --> 00:00:56,798 合闸指示灯HG 24 00:00:56,798 --> 00:01:00,853 通过连接一个真空断路器的常开点用于指示合闸 25 00:01:00,853 --> 00:01:04,643 分闸指示灯HR连接一个真空断路器的常闭点 26 00:01:04,643 --> 00:01:05,993 用于指示分闸