1 00:00:00,000 --> 00:00:02,930 KYN28柜属于中置式开关柜 2 00:00:02,930 --> 00:00:05,400 该型开关柜主要用于10kV 3 00:00:05,400 --> 00:00:08,360 6kV等电力系统的电能分配与控制 4 00:00:08,360 --> 00:00:10,245 通过金属板材拼接 5 00:00:10,245 --> 00:00:11,350 将低压室 6 00:00:11,350 --> 00:00:12,415 断路器式 7 00:00:12,415 --> 00:00:13,345 母线室 8 00:00:13,345 --> 00:00:14,775 电缆式等隔离 9 00:00:14,775 --> 00:00:15,893 模块化设计 10 00:00:15,893 --> 00:00:18,333 确保了各功能区互不干扰 11 00:00:18,334 --> 00:00:21,609 操作系统和智能组合电气可灵活搭配 12 00:00:21,609 --> 00:00:22,734 实现操控 13 00:00:22,734 --> 00:00:23,514 检测 14 00:00:23,514 --> 00:00:24,600 保护等功能 15 00:00:24,600 --> 00:00:28,560 通过高压断路器实现电路的接通、分断及保护 16 00:00:28,561 --> 00:00:30,516 并且派生出了计量柜 17 00:00:30,516 --> 00:00:31,386 PT柜 18 00:00:31,386 --> 00:00:32,431 进线柜等 19 00:00:32,431 --> 00:00:35,614 组合后让其成为整套高压柜的不二之选 20 00:00:35,614 --> 00:00:37,624 相较于固定式开关柜 21 00:00:37,624 --> 00:00:39,789 采用小车式断路器结构 22 00:00:39,789 --> 00:00:41,667 便于设备的维护与更换 23 00:00:41,667 --> 00:00:44,472 提升了操作灵活性和检修效率 24 00:00:44,472 --> 00:00:46,662 五防连锁机构的可靠设计 25 00:00:46,662 --> 00:00:48,552 也保证了设备和人员的安全 26 00:00:49,095 --> 00:00:51,268 现在模拟一下他的操控 27 00:00:51,268 --> 00:00:53,441 检修位置到试验位置 28 00:00:53,441 --> 00:00:56,335 首先将断路器放到移动手车上 29 00:00:56,335 --> 00:00:59,095 然后将手车调整到合适高度 30 00:00:59,095 --> 00:01:01,761 将手车插到连接控并锁死 31 00:01:01,762 --> 00:01:03,842 双手向里推动拉杆 32 00:01:03,842 --> 00:01:06,028 听到咔哒声后往里推 33 00:01:06,028 --> 00:01:07,962 缓慢将手车推入 34 00:01:07,962 --> 00:01:11,215 松开双手让手柄自复位卡进锁孔 35 00:01:11,215 --> 00:01:12,908 插上航空插头 36 00:01:12,908 --> 00:01:16,068 用手车摇把向里推动并缓慢摇动 37 00:01:16,069 --> 00:01:17,815 听到机械咔哒声 38 00:01:17,815 --> 00:01:19,535 并观察指示面板 39 00:01:19,535 --> 00:01:21,589 看到面板指示灯亮起 40 00:01:21,589 --> 00:01:23,469 说明到达实验位置 41 00:01:23,469 --> 00:01:25,802 实验位置到达工作位置 42 00:01:25,802 --> 00:01:28,269 首先需观查两个先决条件 43 00:01:28,269 --> 00:01:31,069 指示面板接地刀闸是否在合位 44 00:01:31,069 --> 00:01:33,389 如果合位需先分开刀闸 45 00:01:33,389 --> 00:01:35,669 观查断路器是否在分位 46 00:01:35,669 --> 00:01:37,069 如果在合位 47 00:01:37,069 --> 00:01:38,762 需先手动分闸 48 00:01:38,762 --> 00:01:40,215 满足条件后 49 00:01:40,216 --> 00:01:42,096 可以继续摇动摇把 50 00:01:42,096 --> 00:01:43,936 随着断路器往里进 51 00:01:43,936 --> 00:01:46,309 活门在底部杠杆下打开 52 00:01:46,310 --> 00:01:47,910 梅花插头进入 53 00:01:47,910 --> 00:01:49,656 直到一声咔哒声 54 00:01:49,656 --> 00:01:51,256 摇把明显卡顿 55 00:01:51,256 --> 00:01:52,110 摇不动 56 00:01:52,110 --> 00:01:54,683 指示面板显示进入工作位置 57 00:01:54,683 --> 00:01:56,256 说明到达位置 58 00:01:56,256 --> 00:01:58,163 摇动时如果摇不动 59 00:01:58,164 --> 00:01:59,444 则需停止 60 00:01:59,444 --> 00:02:01,804 检查机械结构是否卡顿 61 00:02:01,804 --> 00:02:04,417 然后再进行分合闸操作即可