1 00:00:00,000 --> 00:00:05,940 220千伏LW25断路器采用三相分体单端口结构 2 00:00:05,940 --> 00:00:08,266 每个产品由三个单极结构 3 00:00:08,266 --> 00:00:09,511 操作简单 4 00:00:09,511 --> 00:00:10,896 可单极操作 5 00:00:10,896 --> 00:00:12,796 也可三极一起操作 6 00:00:12,796 --> 00:00:15,231 便于安装和操作是变电站 7 00:00:15,240 --> 00:00:19,453 发电厂 以及输电线路理想的高压设备 8 00:00:19,454 --> 00:00:23,074 它具有优异的热稳定性和机械耐久性 9 00:00:23,074 --> 00:00:26,409 能够在恶劣的工作环境中长时间稳定运行 10 00:00:27,001 --> 00:00:30,586 首先储能时是断路器通过电机旋转 11 00:00:30,586 --> 00:00:33,987 电机齿轮联动两个棘爪交替偏心运动 12 00:00:33,987 --> 00:00:35,597 联动拉动滚轮 13 00:00:35,597 --> 00:00:37,627 带动竖轴向上运动 14 00:00:37,627 --> 00:00:40,447 带动合闸弹簧压缩变短从而储能 15 00:00:41,041 --> 00:00:43,056 合闸弹簧系统独立 16 00:00:43,056 --> 00:00:44,261 操作稳定 17 00:00:44,261 --> 00:00:46,101 合闸电磁铁吸合 18 00:00:46,101 --> 00:00:47,831 铁芯向上运动 19 00:00:47,831 --> 00:00:49,294 带动闸锁旋转 20 00:00:49,294 --> 00:00:50,964 从而释放滚轮 21 00:00:50,964 --> 00:00:53,294 在合闸储能弹簧变长 22 00:00:53,294 --> 00:00:54,919 滚轮开始运动 23 00:00:54,919 --> 00:00:57,974 同时轴凸轮撞击连杆逆时针运动 24 00:00:57,974 --> 00:00:59,679 使杆向下运动 25 00:00:59,679 --> 00:01:04,479 同时拉动分闸储能杆向上运动对分闸弹簧进行储能 26 00:01:04,481 --> 00:01:06,716 带动拐臂顺时针旋转 27 00:01:06,716 --> 00:01:08,381 拉杆向前运动 28 00:01:08,381 --> 00:01:12,211 带动拐臂顺时针旋转拉动触头杆向上运动 29 00:01:12,214 --> 00:01:14,721 插入静触头完成合闸 30 00:01:14,721 --> 00:01:16,746 分闸弹簧释放系统 31 00:01:16,746 --> 00:01:19,026 首先分闸电磁铁吸合 32 00:01:19,026 --> 00:01:20,706 铁芯向上运动 33 00:01:20,706 --> 00:01:22,161 推动分闸掣子 34 00:01:22,161 --> 00:01:23,971 压到触发联动杆 35 00:01:23,971 --> 00:01:26,551 触发联动杆撞击锁死机构 36 00:01:26,551 --> 00:01:28,671 使主轴顺时针旋转 37 00:01:28,671 --> 00:01:30,414 释放对主轴的束缚 38 00:01:30,414 --> 00:01:33,449 联动机构输出拐臂顺时针旋转 39 00:01:33,449 --> 00:01:35,499 推动竖轴向下运动 40 00:01:35,499 --> 00:01:37,854 分闸弹簧变长释放能量 41 00:01:37,854 --> 00:01:39,249 轴向上运动 42 00:01:39,249 --> 00:01:41,519 拉动拐臂逆时针旋转 43 00:01:41,519 --> 00:01:43,214 拉杆向后运动 44 00:01:43,214 --> 00:01:45,267 拉动拐臂逆时针旋转 45 00:01:45,267 --> 00:01:49,601 使动触头杆向下运动脱离静触点完成分闸 46 00:01:49,601 --> 00:01:55,054 整机经历了5000次不间断的机械寿命试验 操作可靠性高 47 00:01:55,055 --> 00:01:57,005 无漏油、漏气风险 48 00:01:57,005 --> 00:02:00,790 且断路器本体与操做机构采用直接连接 49 00:02:00,790 --> 00:02:03,188 使得它体积小、重量轻 50 00:02:03,189 --> 00:02:05,534 高可靠的弹簧操动机构 51 00:02:05,534 --> 00:02:07,409 使结构简单清晰 52 00:02:07,409 --> 00:02:09,869 产品运行维护工作量很少 53 00:02:09,869 --> 00:02:14,722 只需定期查看六氟化硫气体表压和涂抹润滑脂即可