1 00:00:00,000 --> 00:00:03,100 KYN28柜属于中置式开关柜 2 00:00:03,100 --> 00:00:05,710 该型开关柜主要用于10kV 3 00:00:05,710 --> 00:00:08,840 6kV等电力系统的电能分配与控制 4 00:00:08,840 --> 00:00:10,840 通过金属板材拼接 5 00:00:10,840 --> 00:00:12,010 将低压室 6 00:00:12,010 --> 00:00:13,140 断路器式 7 00:00:13,140 --> 00:00:14,120 母线室 8 00:00:14,120 --> 00:00:15,430 电缆式隔离 9 00:00:15,430 --> 00:00:16,580 模块化设计 10 00:00:16,586 --> 00:00:19,173 确保了各功能区互不干扰 11 00:00:19,174 --> 00:00:22,634 操作系统和智能组合电气可灵活搭配 12 00:00:22,634 --> 00:00:23,814 实现操控 13 00:00:23,814 --> 00:00:24,634 检测 14 00:00:24,634 --> 00:00:25,627 保护功能 15 00:00:25,627 --> 00:00:29,814 通过高压断路器实现电路的接通、分断及保护 16 00:00:29,814 --> 00:00:31,884 并且派生出了计量柜 17 00:00:31,884 --> 00:00:32,804 PT柜 18 00:00:32,804 --> 00:00:33,914 进线柜等 19 00:00:33,914 --> 00:00:37,267 组合后让其成为整套高压柜的不二之选 20 00:00:37,267 --> 00:00:39,387 相较于固定式开关柜 21 00:00:39,387 --> 00:00:41,667 采用小车式断路器结构 22 00:00:41,667 --> 00:00:43,667 便于设备的维护与更换 23 00:00:43,667 --> 00:00:46,627 提升了操作灵活性和检修效率 24 00:00:46,627 --> 00:00:48,957 五防连锁机构的可靠设计 25 00:00:48,957 --> 00:00:50,957 也保证了设备和人员的安全 26 00:00:51,521 --> 00:00:53,801 检修位置到试验位置 27 00:00:53,801 --> 00:00:56,867 首先将断路器放到移动手车上 28 00:00:56,868 --> 00:00:59,788 然后将手车调整到合适高度 29 00:00:59,788 --> 00:01:02,614 将手车插到连接控并锁死 30 00:01:02,615 --> 00:01:04,748 双手向里推动拉杆 31 00:01:04,748 --> 00:01:07,055 听到咔哒声后往里推 32 00:01:07,055 --> 00:01:09,055 缓慢将手车推入 33 00:01:09,055 --> 00:01:12,468 松开双手让手柄自复位卡进锁孔 34 00:01:12,468 --> 00:01:14,255 插上航空插头 35 00:01:14,255 --> 00:01:16,495 用手车摇把缓慢摇动 36 00:01:16,495 --> 00:01:18,175 听到清脆响动 37 00:01:18,175 --> 00:01:19,988 并观察指示面板 38 00:01:19,988 --> 00:01:22,295 看到面板指示灯亮起 39 00:01:22,295 --> 00:01:24,281 说明到达实验位置 40 00:01:24,281 --> 00:01:26,748 实验位置到达工作位置 41 00:01:26,748 --> 00:01:29,175 首先观查两个先决条件 42 00:01:29,175 --> 00:01:32,135 指示面板接地刀闸是否在合位 43 00:01:32,135 --> 00:01:34,575 如果合位需先分开刀闸 44 00:01:34,575 --> 00:01:36,988 观查断路器是否在分位 45 00:01:36,988 --> 00:01:38,455 如果在合位 46 00:01:38,455 --> 00:01:40,255 需先手动分闸 47 00:01:40,255 --> 00:01:42,948 没问题就可以继续摇动摇把 48 00:01:42,948 --> 00:01:45,055 随着断路器往里进 49 00:01:45,055 --> 00:01:47,535 活门在底部杠杆下打开 50 00:01:47,535 --> 00:01:49,295 梅花插头进入 51 00:01:49,295 --> 00:01:51,095 直到一声卡巴声 52 00:01:51,095 --> 00:01:54,575 摇不动 指示面板显示进入工作位置 53 00:01:54,575 --> 00:01:56,241 说明到达位置 54 00:01:56,241 --> 00:01:58,401 摇动时如果摇不动 55 00:01:58,401 --> 00:01:59,575 则停止 56 00:01:59,575 --> 00:02:02,081 检查机械结构是否卡顿 57 00:02:02,082 --> 00:02:04,655 然后进行分合闸操作即可