@@ -1,180 +1,312 @@
|
|
|
1
|
|
|
-00:00:00,000 --> 00:00:03,660
|
|
|
-1.该二次线路具备手动本地分合闸功能
|
|
|
+00:00:00,000 --> 00:00:04,280
|
|
|
+现在让我们模拟一下线路控制 合上空气开关
|
|
|
|
|
|
2
|
|
|
-00:00:03,660 --> 00:00:04,910
|
|
|
-用于本地操作
|
|
|
+00:00:04,280 --> 00:00:07,210
|
|
|
+假设此时的线路处于分闸状态
|
|
|
|
|
|
3
|
|
|
-00:00:04,910 --> 00:00:06,080
|
|
|
-远程分合闸
|
|
|
+00:00:07,210 --> 00:00:09,240
|
|
|
+此时分闸指式灯点亮
|
|
|
|
|
|
4
|
|
|
-00:00:06,080 --> 00:00:10,960
|
|
|
-用于远程自动化或者国网平台或者远控箱分合闸功能
|
|
|
+00:00:09,240 --> 00:00:11,260
|
|
|
+分闸位置继电器吸合
|
|
|
|
|
|
5
|
|
|
-00:00:10,960 --> 00:00:14,250
|
|
|
-当分合闸旋钮KK打到本地控制时
|
|
|
+00:00:11,266 --> 00:00:13,376
|
|
|
+而由于两个电器的分压
|
|
|
|
|
|
6
|
|
|
-00:00:14,250 --> 00:00:15,910
|
|
|
-可旋至手动合闸
|
|
|
+00:00:13,376 --> 00:00:16,096
|
|
|
+致使合闸电磁铁只通电而没有吸合
|
|
|
|
|
|
7
|
|
|
-00:00:15,910 --> 00:00:17,706
|
|
|
-让KK1 2接通
|
|
|
+00:00:16,654 --> 00:00:19,904
|
|
|
+这样的好处就是可以检测其是否好坏
|
|
|
|
|
|
8
|
|
|
-00:00:17,706 --> 00:00:21,120
|
|
|
-使合闸线圈HQ吸合 用于合闸
|
|
|
+00:00:19,904 --> 00:00:21,984
|
|
|
+当合闸电磁铁损害时
|
|
|
|
|
|
9
|
|
|
-00:00:21,120 --> 00:00:27,480
|
|
|
-当旋钮钮到分闸时 11 12端子接通 使分闸线圈TQ跳闸
|
|
|
+00:00:21,984 --> 00:00:23,384
|
|
|
+分闸指示灯会熄灭
|
|
|
|
|
|
10
|
|
|
-00:00:27,480 --> 00:00:32,440
|
|
|
-当选至远程时5 6端子接通 7 8端子接通
|
|
|
+00:00:23,934 --> 00:00:26,034
|
|
|
+我们先进行手动合闸
|
|
|
|
|
|
11
|
|
|
-00:00:32,440 --> 00:00:35,780
|
|
|
-可用远程合闸入口和远程分闸入口
|
|
|
+00:00:26,034 --> 00:00:28,524
|
|
|
+我们将旋钮达到手动合闸
|
|
|
|
|
|
12
|
|
|
-00:00:35,780 --> 00:00:37,170
|
|
|
-接到国网平台
|
|
|
+00:00:28,524 --> 00:00:31,627
|
|
|
+电首先到达kkj继电器让其吸合
|
|
|
|
|
|
13
|
|
|
-00:00:37,170 --> 00:00:38,140
|
|
|
-远控箱去
|
|
|
+00:00:31,627 --> 00:00:36,227
|
|
|
+经二极管 吸合合闸保持继电器和合闸电磁铁
|
|
|
|
|
|
14
|
|
|
-00:00:38,140 --> 00:00:40,093
|
|
|
-去分合闸断路器
|
|
|
+00:00:36,228 --> 00:00:38,188
|
|
|
+此时由于电走捷径
|
|
|
|
|
|
15
|
|
|
-00:00:40,094 --> 00:00:43,664
|
|
|
-2.该线路可通过接入微机综合保护器
|
|
|
+00:00:38,188 --> 00:00:39,838
|
|
|
+分闸指示灯熄灭
|
|
|
|
|
|
16
|
|
|
-00:00:43,664 --> 00:00:47,760
|
|
|
-让其具备二次重合闸功能和远程跳闸功能
|
|
|
+00:00:39,838 --> 00:00:41,978
|
|
|
+分闸位置继电器恢复
|
|
|
|
|
|
17
|
|
|
-00:00:47,761 --> 00:00:50,871
|
|
|
-来自微机保护器的重合闸常开点HJ
|
|
|
+00:00:41,978 --> 00:00:44,388
|
|
|
+其合闸自保触点也会吸合
|
|
|
|
|
|
18
|
|
|
-00:00:50,871 --> 00:00:52,631
|
|
|
-可使意外跳闸时
|
|
|
+00:00:44,388 --> 00:00:47,018
|
|
|
+自保触点用于当旋钮复位后
|
|
|
|
|
|
19
|
|
|
-00:00:52,631 --> 00:00:53,961
|
|
|
-根据微保设置
|
|
|
+00:00:47,018 --> 00:00:49,748
|
|
|
+线路一直保持合闸电磁吸合
|
|
|
|
|
|
20
|
|
|
-00:00:53,961 --> 00:00:55,667
|
|
|
-来一次重合闸
|
|
|
+00:00:49,748 --> 00:00:51,508
|
|
|
+防止中途一半停止
|
|
|
|
|
|
21
|
|
|
-00:00:55,668 --> 00:00:57,548
|
|
|
-当不想利用该功能时
|
|
|
+00:00:51,508 --> 00:00:53,214
|
|
|
+直到合闸完成
|
|
|
|
|
|
22
|
|
|
-00:00:57,548 --> 00:00:58,778
|
|
|
-或者检修时
|
|
|
+00:00:53,215 --> 00:00:55,775
|
|
|
+此时断路器常闭触点分开
|
|
|
|
|
|
23
|
|
|
-00:00:58,778 --> 00:01:00,458
|
|
|
-可挑其保护连片
|
|
|
+00:00:55,775 --> 00:00:57,335
|
|
|
+常开触点吸合
|
|
|
|
|
|
24
|
|
|
-00:01:00,458 --> 00:01:04,681
|
|
|
-远程跳闸TJ保护跳闸入口可接入微机保护
|
|
|
+00:00:57,335 --> 00:00:59,841
|
|
|
+这导致了合闸回路全部熄灭
|
|
|
|
|
|
25
|
|
|
-00:01:04,682 --> 00:01:09,388
|
|
|
-或者其他保护继电器 用于需要跳闸时的跳闸
|
|
|
+00:00:59,841 --> 00:01:01,761
|
|
|
+而合闸指示灯亮起
|
|
|
|
|
|
26
|
|
|
-00:01:09,300 --> 00:01:11,468
|
|
|
-3.该线路具备防跳跃功能
|
|
|
+00:01:01,761 --> 00:01:03,931
|
|
|
+合闸位置继电器吸合
|
|
|
|
|
|
27
|
|
|
-00:01:11,468 --> 00:01:14,655
|
|
|
-TBJV继电器在断路器分闸时吸合
|
|
|
+00:01:03,931 --> 00:01:05,351
|
|
|
+同样由于分压
|
|
|
|
|
|
28
|
|
|
-00:01:14,655 --> 00:01:17,585
|
|
|
-通过它的辅助触点串入合闸回路
|
|
|
+00:01:05,351 --> 00:01:07,135
|
|
|
+电经过分闸电磁铁
|
|
|
|
|
|
29
|
|
|
-00:01:17,585 --> 00:01:21,635
|
|
|
-防止在跳闸过程中又有合闸命令而损坏机构
|
|
|
+00:01:07,135 --> 00:01:10,121
|
|
|
+却由于电压过低无法吸合铁芯
|
|
|
|
|
|
30
|
|
|
-00:01:21,642 --> 00:01:25,752
|
|
|
-4.KKJ是合后继电器也称磁保持继电器
|
|
|
+00:01:10,122 --> 00:01:11,542
|
|
|
+手动分闸时
|
|
|
|
|
|
31
|
|
|
-00:01:25,752 --> 00:01:30,932
|
|
|
-通过D1、D2两个二极管的单相导通性能来保证只有手动合闸
|
|
|
+00:01:11,542 --> 00:01:13,682
|
|
|
+旋钮打到手动分闸
|
|
|
|
|
|
32
|
|
|
-00:01:30,932 --> 00:01:32,162
|
|
|
-才能让其动作
|
|
|
+00:01:13,682 --> 00:01:16,182
|
|
|
+此时电到达kkj继电器
|
|
|
|
|
|
33
|
|
|
-00:01:32,162 --> 00:01:34,072
|
|
|
-动作后不自动返回
|
|
|
+00:01:16,182 --> 00:01:18,322
|
|
|
+此继电器是保持继电器
|
|
|
|
|
|
34
|
|
|
-00:01:34,072 --> 00:01:37,632
|
|
|
-手动跳闸或者自动合闸后才能让其复归
|
|
|
+00:01:18,322 --> 00:01:19,692
|
|
|
+合闸时亮起
|
|
|
|
|
|
35
|
|
|
-00:01:37,642 --> 00:01:40,055
|
|
|
-其接点可以用于重合闸
|
|
|
+00:01:19,692 --> 00:01:21,992
|
|
|
+直到分闸信号到达熄灭
|
|
|
|
|
|
36
|
|
|
-00:01:40,056 --> 00:01:44,366
|
|
|
-5.HYI与TYJ是合闸和跳闸压力继电器
|
|
|
+00:01:21,992 --> 00:01:24,202
|
|
|
+可将辅助触点做为备用
|
|
|
|
|
|
37
|
|
|
-00:01:44,366 --> 00:01:46,696
|
|
|
-接入断路器机构的气压接点
|
|
|
+00:01:24,202 --> 00:01:25,942
|
|
|
+用于重合闸的先决条件
|
|
|
|
|
|
38
|
|
|
-00:01:46,696 --> 00:01:50,116
|
|
|
-在以六氟化硫为灭弧绝缘介质的开关中
|
|
|
+00:01:26,509 --> 00:01:28,199
|
|
|
+后经二极管往上
|
|
|
|
|
|
39
|
|
|
-00:01:50,116 --> 00:01:52,429
|
|
|
-如果六氟化硫气体有泄露
|
|
|
+00:01:28,199 --> 00:01:31,159
|
|
|
+此二极管是利用其单向导通性
|
|
|
|
|
|
40
|
|
|
-00:01:52,429 --> 00:01:57,189
|
|
|
-则当气体压力降至危及灭弧时该接点T1和T2导通
|
|
|
+00:01:31,159 --> 00:01:34,642
|
|
|
+防止电从别的入口进入影响我们线路控制
|
|
|
|
|
|
41
|
|
|
-00:01:57,189 --> 00:01:58,849
|
|
|
-将操作回路断开
|
|
|
+00:01:34,642 --> 00:01:38,222
|
|
|
+使跳闸保持继电器和分闸电磁铁吸合
|
|
|
|
|
|
42
|
|
|
-00:01:58,856 --> 00:02:00,176
|
|
|
-禁止操作
|
|
|
+00:01:38,222 --> 00:01:40,909
|
|
|
+两个分闸自保辅助触点也吸合
|
|
|
|
|
|
43
|
|
|
-00:02:00,176 --> 00:02:04,706
|
|
|
-6.位置继电器HWJ TWT的作用有两个
|
|
|
+00:01:40,909 --> 00:01:45,309
|
|
|
+合闸指式灯会熄灭 合闸位置继电器也会复位
|
|
|
|
|
|
44
|
|
|
-00:02:04,706 --> 00:02:06,789
|
|
|
-一是显示当前开关位置
|
|
|
+00:01:45,309 --> 00:01:46,689
|
|
|
+分闸完成后
|
|
|
|
|
|
45
|
|
|
-00:02:06,789 --> 00:02:09,576
|
|
|
-二是监视跳、合线圈是否完好
|
|
|
+00:01:46,689 --> 00:01:48,869
|
|
|
+断路器常开触点分开
|
|
|
+
|
|
|
+46
|
|
|
+00:01:48,869 --> 00:01:50,419
|
|
|
+常闭触点吸合
|
|
|
+
|
|
|
+47
|
|
|
+00:01:50,419 --> 00:01:51,735
|
|
|
+分闸指示点亮
|
|
|
+
|
|
|
+48
|
|
|
+00:01:51,735 --> 00:01:53,869
|
|
|
+线路回到最初位置
|
|
|
+
|
|
|
+49
|
|
|
+00:01:53,869 --> 00:01:55,459
|
|
|
+当远程合闸时
|
|
|
+
|
|
|
+50
|
|
|
+00:01:55,459 --> 00:01:57,579
|
|
|
+我们将旋钮打到远程
|
|
|
+
|
|
|
+51
|
|
|
+00:01:57,579 --> 00:01:59,359
|
|
|
+此时5 6接通
|
|
|
+
|
|
|
+52
|
|
|
+00:01:59,359 --> 00:02:01,509
|
|
|
+当远程合闸入口吸合时
|
|
|
+
|
|
|
+53
|
|
|
+00:02:01,509 --> 00:02:03,999
|
|
|
+同样会吸合kkj继电器
|
|
|
+
|
|
|
+54
|
|
|
+00:02:03,999 --> 00:02:05,499
|
|
|
+和合闸电磁铁
|
|
|
+
|
|
|
+55
|
|
|
+00:02:05,499 --> 00:02:07,129
|
|
|
+让异地控制成为了可能
|
|
|
+
|
|
|
+56
|
|
|
+00:02:07,683 --> 00:02:10,373
|
|
|
+我们假设线路出现了短路故障
|
|
|
+
|
|
|
+57
|
|
|
+00:02:10,373 --> 00:02:13,429
|
|
|
+此时微机保护的保护跳闸入口吸合
|
|
|
+
|
|
|
+58
|
|
|
+00:02:13,429 --> 00:02:18,829
|
|
|
+线路经保护连片 可继续走我们的分闸线路 完成跳闸
|
|
|
+
|
|
|
+59
|
|
|
+00:02:18,830 --> 00:02:23,250
|
|
|
+由于高电压效线路故障百分之八十的故障是瞬时的
|
|
|
+
|
|
|
+60
|
|
|
+00:02:23,250 --> 00:02:26,070
|
|
|
+我们的微机保护会提供重合闸功能
|
|
|
+
|
|
|
+61
|
|
|
+00:02:26,070 --> 00:02:28,010
|
|
|
+让重合闸入口吸合
|
|
|
+
|
|
|
+62
|
|
|
+00:02:28,010 --> 00:02:31,640
|
|
|
+线路会到达合闸电磁铁完成一次重合闸
|
|
|
+
|
|
|
+63
|
|
|
+00:02:31,640 --> 00:02:33,480
|
|
|
+大大提高了线路的可靠性
|
|
|
+
|
|
|
+64
|
|
|
+00:02:34,044 --> 00:02:35,864
|
|
|
+当我们远程分闸时
|
|
|
+
|
|
|
+65
|
|
|
+00:02:35,864 --> 00:02:38,624
|
|
|
+将远程分闸入口7 8吸合
|
|
|
+
|
|
|
+66
|
|
|
+00:02:38,624 --> 00:02:40,870
|
|
|
+假设我们在没有完成分闸时
|
|
|
+
|
|
|
+67
|
|
|
+00:02:40,870 --> 00:02:43,810
|
|
|
+重合闸或者本地误操作了合闸
|
|
|
+
|
|
|
+68
|
|
|
+00:02:43,810 --> 00:02:46,760
|
|
|
+此时电会首先到达防跳跃继电器
|
|
|
+
|
|
|
+69
|
|
|
+00:02:46,764 --> 00:02:47,964
|
|
|
+让其吸合
|
|
|
+
|
|
|
+70
|
|
|
+00:02:47,964 --> 00:02:48,954
|
|
|
+并自锁
|
|
|
+
|
|
|
+71
|
|
|
+00:02:48,954 --> 00:02:51,654
|
|
|
+导致放跳跃辅助常闭点打开
|
|
|
+
|
|
|
+72
|
|
|
+00:02:51,654 --> 00:02:53,084
|
|
|
+切断了合闸回路
|
|
|
+
|
|
|
+73
|
|
|
+00:02:53,084 --> 00:02:55,424
|
|
|
+使合闸电磁铁不能吸合
|
|
|
+
|
|
|
+74
|
|
|
+00:02:55,424 --> 00:02:58,114
|
|
|
+保护了断路器的机械结构和误操作
|
|
|
+
|
|
|
+75
|
|
|
+00:02:58,684 --> 00:03:00,174
|
|
|
+当失误恢复后
|
|
|
+
|
|
|
+76
|
|
|
+00:03:00,174 --> 00:03:02,284
|
|
|
+而分闸系统不受影响
|
|
|
+
|
|
|
+77
|
|
|
+00:03:02,284 --> 00:03:03,954
|
|
|
+会继续完成分闸
|
|
|
+
|
|
|
+78
|
|
|
+00:03:03,954 --> 00:03:05,590
|
|
|
+直到分闸完成
|
|
|
|